Rockwell Automation Publication 20D-TD002L-EN-P - July 2018 33
PowerFlex 700S Drives with Phase II Control
Other types of shielded cable are available, but the selection of these types may limit the allowable cable length.
Particularly, some of the newer cables twist 4 conductors of THHN wire and wrap them tightly with a foil shield. This
construction can greatly increase the cable charging current required and reduce the overall drive performance. Unless
specified in the individual distance tables as tested with the drive, these cables are not recommended and their
performance against the lead length limits supplied is not known.
Maximum Motor Cable Lengths
For the Terminator, the maximum cable length is 182.9 meters (600 feet) for 400/480/600V drives (not 690V).
The PWM frequency must be 2 kHz. The 1204-TFA1 can be used only on low HP (5 HP and below), while the
1204-TFB2 can be used from 2…800 HP.
1204 Reflected Wave Reduction Device (all motor insulation classes):
1204-RWR2-09
2 kHz: 182.9 m (600 ft.) at 400/480V and 121.9 m (400 ft.) at 600V.
4 kHz: 91.4 m (300 ft.) at 400/480V and 61.0 m (200 ft.) at 600V.
1204-RWC-17
2 kHz: 365.8 m (1200 ft.) at 400/480/600V.
4 kHz: 243.8 m (800 ft.) at 400/480V and 121.9 m (400 ft.) at 600V.
For both devices, power dissipation in the damping resistor limits maximum cable length.
The 1321-RWR is a complete reflected wave reduction solution available for many of the PowerFlex drives. If
available, a 1321-RWR catalog number will be indicated in the “Reactor/RWR” column. When not available, use
the reactor and resistor information that is provided to build a solution.
Location Rating/Type Description
Standard (Option 1) 600V, 90C (194F)
XHHW2/RHW-2
Anixter B209500-B209507, Belden 29501-29507, or
equivalent
Four tinned copper conductors with XLPE insulation.
Copper braid/aluminum foil combination shield and tinned copper drain wire.
PVC jacket.
Standard (Option 2) Tray rated 600V, 90 C (194 F) RHH/RHW-2
Anixter OLF-7xxxxx or equivalent
Three tinned copper conductors with XLPE insulation.
5 mil single helical copper tape (25% overlap min.) with three bare copper grounds in contact
with shield.
PVC jacket.
Class I & II;
Division I & II
Tray rated 600V, 90 C (194 F) RHH/RHW-2
Anixter 7V-7xxxx-3G or equivalent
Three bare copper conductors with XLPE insulation and impervious corrugated continuously
welded aluminum armor.
Black sunlight resistant PVC jacket overall.
Three copper grounds on #10 AWG and smaller.
IMPORTANT In the following tables, A ” in any of the latter columns will indicate that this drive rating can be used with an Allen-Bradley
Terminator (1204-TFA1/1204-TFB2) and/or Reflected Wave Reduction Device with Common Mode Choke (1204-RWC-17) or
without choke (1204-RWR2).
For Further Information on ... See Publication...
1321-RWR 1321-TD001
1204-RWR2 1204-5.1
1204-RWC 1204-IN001
1204-TFxx 1204-IN002