40 Rockwell Automation Publication 20D-TD002L-EN-P - July 2018
PowerFlex 700S Drives with Phase II Control
Frame 9 Terminal Block Locations
No. Name Description Wire Size Range
(3)
(3) Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
Torque
Maximum Minimum Recommended
1
Input Power Terminal Block
(1)
L1, L2, L3
(1) Do Not exceed maximum wire size. Parallel connections may be required.
Input power 185.0 mm
2
(350 MCM)
95.0 mm
2
(4/0 AWG)
40 N•m
(354 lb•in)
2
Output Power Terminal Block
(1)
U/T1, V/T2, W/T3
Motor connections 185.0 mm
2
(350 MCM)
95.0 mm
2
(4/0 AWG)
40 N•m
(354 lb•in)
3
SHLD Terminal, PE, Motor Ground Terminating point for wiring shields 95.0 mm
2
(4/0 AWG)
5.0 mm2
(10 AWG)
22 N•m
(195 lb•in)
4
DC Bus
(2)
(2 Terminals; DC–, DC+)
(2) DC terminal and brake lugs can be removed.
DC input or external brake
(Internal Brake option not ordered)
185.0 mm
2
(350 MCM)
95.0 mm
2
(4/0 AWG)
40 N•m
(354 lb•in)
DC Bus w/Brake
(2)
(3 Terminals; DC–, DC+/R+, R–)
DC input/internal brake
(Internal Brake option is ordered)
185.0 mm
2
(350 MCM)
95.0 mm
2
(4/0 AWG)
40 N•m
(354 lb•in)
5
Cable Clamp for Shield
DC –
DC+/R+
R–
DC –
DC+/R+
R–
L1
AC Line Input Power To Motor Leads
L2 L3 L1 L2 L3 U/T1 V/T2 W/T3 U/T1 V/T2 W/T3
1
2
3
4
5