52 Rockwell Automation Publication 20D-TD002L-EN-P - July 2018
PowerFlex 700S Drives with Phase II Control
400 Volt AC Input Frames 1…6 Drive Ratings
20DB192 6 75 – 4 50 180 74.9 192 211 288 2043
– 60 4 50 145 60.1 154 231 308 2043
20DB260 6 100 – 2 45 233 96.8 260 286 390 2305
– 75 2 50 169 74.9 205 305 410 2305
(1) The temperature rating that is listed for frame size 1…4 drives is for NEMA/UL open types only. The adhesive tape label must be removed in order to operate
at this temperature, otherwise the ambient operating temperature of these drives is 40 °C.
Drive Catalog
Number
Frame
kW Rating PWM
Freq.
Temp.
(3)
(3) The temperature rating that is listed for frame size 1…4 drives is for NEMA/UL open types only. The adhesive tape label must be removed in order to operate at
this temperature, otherwise the ambient operating temperature of these drives is 40 °C.
Input Ratings Output Amps Watts
Loss
ND HD kHz C Amps kVA Cont. 1 Min. 3 Sec.
20DC2P1 1 0.75 0.55 4 50 1.8 1.3 2.1 2.4 3.2 103
20DC3P5 1 1.5 1.1 4 50 3.2 2.2 3.5 4.5 6.0 117
20DC5P0 1 2.2 1.5 4 50 4.6 3.2 5.0 5.5 7.5 135
20DC8P7 1 4 3.0 4 50 7.9 5.5 8.7 9.9 13.2 210
20DC011 1 5.5 4 4 50 10.8 7.5 11.5 13 17.4 243
20DC015 1 7.5 5.5 4 50 14.4 10.0 15.4 17.2 23.1 271
20DC022 1 11 7.5 4 50 20.6 14.3 22 24.2 33 389
20DC030 2 15 11 4 50 28.4 19.7 30 33 45 467
20DC037 2 18.5 15 4 50 35.0 24.3 37 45 60 519
20DC043 3 22 18.5 4 50 40.7 28.2 43 56 74 543
20DC056 3 30 22 4 50 53 36.7 56 64 86 708
20DC072 3 37 30 4 45 68.9 47.8 72 84 112 767
20DC085
(1)
(1) 20DC085 current rating is limited to 45° C ambient.
4 45 – 4 50 81.4 56.4 85 94 128 908
– 37 4 50 68.9 47.8 72 108 144 908
20DC105 5 55 – 4 50
(4)
(4) UL Type 12/IP54 (flange mount) heatsink ambient temperature rating is 40 C/ambient of unprotected drive portion (inside enclosure) is 55 C. The ambient
temperature for the UL Type 12/IP54 standalone drives is 40 C.
100.5 69.6 105 116 158 1157
–454 50
(4)
81.4 56.4 85 128 170 1157
20DC125 5 55 – 4 50
(4)
121.1 83.9 125 138 163 1157
– 45 4 50
(4)
101 63.7 96 144 168 1157
20DC140 5 75 – 4 50
(4)
135.6 94 140 154 210 1529
–554 50
(4)
121 69.6 105 158 210 1529
20DC170 6 90 – 4 50
(4)
164.6 114 170 187 255 1895
– 75 4 50
(4)
136 94 140 210 280 1895
20DC205
(2)
(2) 20DC205 current rating is limited to 40° C ambient.
6 110 – 4 40
(4)
198.5 138 205 220 289 2254
–904 40
(4)
164 114 170 255 313 2254
20DC260 6 132 – 2 40
(4)
254.7 166 260 286 390 2553
– 110 2 40
(4)
199 138 205 308 410 2553
240 Volt AC Input Frames 1…6 Drive Ratings (continued)
Drive Catalog
Number
Frame
HP Rating PWM
Freq.
Temp.
(1)
Input Ratings Output Amps Watts
Loss
ND HD kHz C Amps kVA Cont. 1 Min. 3 Sec.