54 Rockwell Automation Publication 20D-TD002L-EN-P - July 2018
PowerFlex 700S Drives with Phase II Control
480 Volt AC Input Frames 9…13 Drive Ratings
20DD096 5 75 – 4 50
(2)
90.1 74.9 96 106 144 1157
–604 50
(2)
72.3 60.1 77 116 154 1157
20DD125 5 100 – 4 50
(2)
117 97.6 125 138 163 1529
– 75 4 50
(2)
90.1 74.9 96 144 168 1529
20DD156 6 125 – 4 50
(2)
146.5 121.7 156 172 234 1895
– 100 4 50
(2)
131 97.6 125 188 250 1895
20DD180 6 150 – 4 50
(2)
169 140.5 180 198 270 2254
– 125 4 50
(2)
147 121.7 156 234 312 2254
20DD248 6 200 2 40
(2)
232.8 188 248 273 372 2553
150 2 40
(2)
169 140.5 180 270 360 2553
(1) The temperature rating that is listed for frame size 1…4 drives is for NEMA/UL open types only. The adhesive tape label must be removed in order to
operate at this temperature, otherwise the ambient operating temperature of these drives is 40 °C.
(2) UL Type 12/IP54 (flange mount) heatsink ambient temperature rating is 40 C/ambient of unprotected drive portion (inside enclosure) is 55 C. The
ambient temperature for the UL Type 12/IP54 standalone drives is 40 C.
Drive Catalog
Number
Frame
HP Rating PWM
Freq.
Temp.
(1)
(1) Maximum air temperature surrounding the drive module.
Input
Ratings
Output Amps Watts Loss
ND HD kHz C Amps Cont. 1 Min. 3 Sec.
20DD261 9 200 - 2 40 252 261 287 410 2700
- 150 2 40 207 205 308 410 2700
20DD300 9 250 - 2 40 290 300 330 450 3100
- 200 2 40 247 245 368 490 3100
20DD385 10 300 - 2 40 372 385 424 600 4320
- 250 2 40 302 300 450 600 4320
20DD460 10 350 - 2 40 444 460 506 770 5335
- 300 2 40 388 385 578 770 5335
20DD500 10 450 - 2 40 483 500 550 750 5921
- 350 2 40 423 420 630 840 5921
20DD590 11 500 - 2 40 570 590 649 956 6620
- 450 2 40 524 520 780 956 6620
20DD650 11 500 - 2 40 628 650 715 1062 7538
- 500 2 40 594 590 885 1062 7538
20DD730 11 600 - 2 40 705 730 803 1095 8312
- 500 2 40 655 650 975 1170 8312
20DD820 12 700 - 2 40 792 820 902 1230 9201
- 600 2 40 735 730 1095 1314 9201
20DD920 12 800 - 2 40 888 920 1012 1380 10670
- 700 2 40 826 820 1230 1476 10670
20DD1K0 12 900 - 2 40 994 1030 1133 1555 11729
- 800 2 35 927 920 1370 1600 11729
20DD1K1 13 1000 - 2 40 1110 1150 1265 1620 13801
- 900 2 40 994 1030 1545 1620 13801
20DD1K3 13 1200 - 2 40 1255 1300 1430 2079 15077
- 1000 2 40 1110 1150 1725 2079 15077
20DD1K4 13 1250 - 2 40 1400 1450 1595 2175 16511
- 1000 2 40 1158 1200 1800 2400 16511
480 Volt AC Input Frames 1…6 Drive Ratings (continued)
Drive Catalog
Number
Frame
HP Rating PWM
Freq.
Temp.
(1)
Input Ratings Output Amps Watts
Loss
ND HD kHz C Amps kVA Cont. 1 Min. 3 Sec.