Rockwell Automation Publication 20D-TD002L-EN-P - July 2018 73
PowerFlex 700S Drives with Phase II Control
325 Volt DC Input Frames 1…6 Drive Protection Devices
20DF750 12 710 – 756 950 (1 per phs)
475 (2 per phs)
1600 950 (1 per phs)
475 (2 per phs)
2200 170M5813 2200 1000
– 630 655 850 (1 per phs)
425 (2 per phs)
1400 850 (1 per phs)
425 (2 per phs)
1900 170M5813 1900 900
20DF820
(1)
12 800 – 826 1100 (1 per phs)
550 (2 per phs)
1800 1100 (1 per phs)
550 (2 per phs)
2400 170M5813 2400 1100
– 630 655 850 (1 per phs)
425 (2 per phs)
1400 850 (1 per phs)
425 (2 per phs)
1900 170M5813 1900 900
20DF920 13 900 – 927 1200 (1 per phs)
600 (2 per phs)
(3)
2000
(3)
1200 (1 per phs)
600 (2 per phs)
(3)
2700
(3)
170M6466
(3)
2700 1200
– 800 826 1100 (1 per phs)
550 (2 per phs)
(3)
1800
(3)
1100 (1 per phs)
550 (2 per phs)
(3)
2400
(3)
170M6466
(3)
2400 1100
20DF1K0 13 1000 – 1038 1300 (1 per phs)
650 (2 per phs)
(3)
2300
(3)
1300 (1 per phs)
650 (2 per phs)
(3)
3000
(3)
170M6466
(3)
3000 1300
– 900 927 1200 (1 per phs)
600 (2 per phs)
(3)
2000
(3)
1200 (1 per phs)
600 (2 per phs)
(3)
2700
(3)
170M6466
(3)
2700 1200
20DF1K1 13 1100 – 1189 1500 (1 per phs)
750 (2 per phs)
(3)
2600
(3)
1500 (1 per phs)
750 (2 per phs)
(3)
3500
(3)
170M6466
(3)
3500 1500
– 1000 1038 1300 (1 per phs)
650 (2 per phs)
(3)
2300
(3)
1300 (1 per phs)
650 (2 per phs)
(3)
3000
(3)
170M6466
(3)
3000 1300
20DF1K5 14 1500 – 1511 1900 (1 per phs)
650 (3 per phs)
3300 1900 (1 per phs)
650 (3 per phs)
4500 170M6466 4500 1900
– 1300 1310 1700 (1 per phs)
575 (3 per phs)
2900 1700 (1 per phs)
575 (3 per phs)
3900 170M6466 3900 1700
(1) 20DF820 drives (ND) are only capable of producing 95% of starting torque under 10 Hz.
(2) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(3) Fuses and disconnect are supplied with AC input NEMA/UL Type 1 drives.
(4) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings that are shown are maximum.
(5) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings that are shown are maximum.
(6) Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(7) Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings that are shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed
1300% FLA.
Drive Catalog Number Frame HP Rating DC Input Ratings Fuse Non-time Delay Fuse
(3)
(3) The power source to Common Bus inverters must be derived from AC Voltages 600V or less, as defined in NFPA70; Art 430-18 (NEC). Battery supplies or
MG sets are not included. The following devices were validated to break current of the derived power DC Bus: Disconnects: Allen-Bradley Bulletin No.
1494, 30A to 400 A; Bulletin No. 194, 30A to 400 A, or ABB: OESA, 600 & 800 A; OESL, all sizes. Fuses: Ferraz Shawmut Type HSJ, all sizes. For any other
devices, please contact the factory.
ND HD Amps
20DB015 1 5 3 16 30 HSJ30
20DB022 1 7.5 5 23.3 45 HSJ45
20DB028 2 10 7.5 30 60 HSJ60
20DB042 3 15 10 45 90 HSJ90
20DB052 3 20 15 55 100 HSJ100
20DB070 4 25 20 75.3 150 HSJ150
20DB080 4 30 25 85.8 175 HSJ175
20DN104
(1)
(1) Catalog number corresponds to output amps for these drives. Drive must be programmed to lower voltage to obtain higher currents that are shown at
right.
5 40 30 114.1 225 HSJ225
20DN130
(1)
5 50 40 142.6 250 HSJ250
20DN154
(1)
6 60 50 169 300 HSJ300
20DN192
(1)
6 75 60 210.6 400 HSJ400
20DN260
(1)(2)
(2) Catalog number corresponds to drives with precharge only.
6 100 75 272.1 400 HSJ400
690 Volt AC Input Frames 9…14 Drive Protection Devices (continued)
Drive
Catalog
Number
Frame
kW Rating Input
Ratings
Dual Element Time Delay Fuse Non-time Delay Fuse Bussmann Style Semi-
conductor Fuse
Circuit
Breaker
(5)
Motor Circuit
Protector
(7)
ND HD Amps Min.
(2)
Max.
(4)
Min.
(2)
Max.
(4)
Max.
(6)
Max.
(6)