Chapter 6 I/O Wiring
Port Assignment
When used in an Integrated Motion application, the Safe Torque Off option 
must be installed in Port 06.
Only one safety option module can be installed at a time. Multiple safety 
options or duplicate safety option installations are not supported.
Jumper Settings
Ensure the hardware enable jumper (ENABLE) on the main control board is 
installed. Refer to page 141
 for location. If not installed, the drive will fault 
when powered up.
Ensure the safety enable jumper (SAFETY) on the main control board is 
removed. Refer to page 142
 for location.