Rockwell Automation Publication 750-IN100B-EN-P - July 2017 129
Power Wiring Chapter 5
Table 14 - PowerFlex 755TM Common Bus Inverter Jumpers
Supply Source 
Type
Grounding Scheme EMC 
Option
PE-A PE-A1 PE-A2 PE-B1
(MOV on the AC 
Precharge 
Control Circuit 
Board)
(MOV in the TVSS 
Module)
(Common Mode 
Caps on All AC 
Common Mode 
Filter Circuit 
Boards)
(Y-Caps on Line 
Side Converter 
Power Interface 
Circuit Boards)
(Y-Caps on Motor 
Side Inverter 
Power Interface 
Circuit Boards)
Regenerative Factory Default C3 N/A N/A N/A N/A Disconnected (Out)
Grounded C2
(2)
N/A N/A N/A N/A TBD
C3 N/A N/A N/A N/A Disconnected (Out)
Ungrounded/High-
resistance Ground 
(1)
N/A N/A N/A N/A N/A Disconnected (Out)
Marine Ungrounded / 
High Resistance 
Ground 
(1)
N/A N/A N/A N/A N/A TBD
Non-Regenerative 
(third-party)
Factory Default C3 N/A N/A N/A N/A Disconnected (Out)
Grounded C2
(2)
N/A N/A N/A N/A TBD
C3 N/A N/A N/A N/A Disconnected (Out)
Ungrounded/High-
resistance Ground 
(1)
N/A N/A N/A N/A N/A Disconnected (Out)
Marine Ungrounded / 
High Resistance 
Ground 
(1)
N/A N/A N/A N/A N/A TBD
(1) Ungrounded and high-resistance ground systems do not meet the EMC Directive due to the disconnected jumper positions.
(2) Full compliance requires an optional EMC solution that is mounted in a dedicated enclosure. Rockwell Automation is evaluating the ability to meet Category C2 compliance. Contact the factory for 
more information.