24 PowerFlex 750-Series Products with TotalFORCE Control
Rockwell Automation Publication 750-PC100A-EN-P - December 2016
Frames 10…12 Input Bay (Typical)
Main Control Board
Frames 10 and 11
Frame 12
Item Name Description
1 HIM Connector DPI Port 1 (HIM Cradle) connection.
2 Control Selector Rotary switch for setting the programming mode.
3 Embedded EtherNet/IP
Address Selectors
Rotary switches for setting lowest octet of EtherNet address (forces
address to 192.168.1.xxx). See the PowerFlex Drives with
TotalFORCE Control Programming Manual, publication 750-PM100
for instructions on setting the IP address.
4 SAFETY Jumper Safety enable jumper. Removed when safety option is installed.
5 ENABLE Jumper Hardware enable jumper. TB1 becomes an Enable when this
jumper is removed.
6 Embedded EtherNet/IP
Connectors
Network cable connections.
7TB1 I/O terminal block.
8 DPI Port 2 Cable connection for handheld and remote HIM options.
Main Control Board TB1 I/O Terminal Designations
Fixed I/O Terminal Name Description
Di 0ac Digital input 0
120V AC (132V AC max)
Connections for AC power supply.
High state: 100…132V AC
Low state: 0…30V AC
Di C Digital input common Digital input common
Di 0dc Digital input 0
24V DC (30V DC max)
Connections for DC power supply.
High state: 20…24V DC
Low state: 0…5V DC
+24V +24 volt power Connections for product supplied 24V
power. 150 mA maximum.
24VC 24 volt common
1
2
3
7
8
6
5
4
Di 0ac
Di C
Di 0dc
+24V
24VC