Publication 2711-UM014B-EN-P
B-14 Messages, Codes and Self-Test Numbers
16402 The CRC check of
the firmware failed
Critical Fault CRC verification failed at startup. Contact technical support.
16403 OS startup failed Critical Fault Operating system failed to start. Contact technical support.
16404 PV Client Task Fault Critical Fault Internal error has occurred. Contact technical support.
16405 Invalid preset
information
received from
motherboard.
Critical Fault Internal error has occurred. Contact technical support.
16406, 16407 Connection with
Addr or scan rate
invalid or no
connection being
attempted.
Critical Fault Internal error has occurred. Contact technical support.
16408 No buffers
available for read
operation
Critical Fault Internal error has occurred. Contact technical support.
16409 DC couldn’t send
out the write
request in time.
Critical Fault Too many write operations are occurring. Contact technical support.
16410 Too many clients
attempted to
connect to server
Critical Fault Internal error has occurred. Contact technical support.
16411 XS-WD creation
error
Critical Fault Internal error has occurred. Contact technical support.
16412 XS-WD start error Critical Fault Internal error has occurred. Contact technical support.
16413 ENet addr is not
valid
Communication
Warning
The EtherNet address for a device on the
EtherNet/IP network is invalid.
Contact technical support.
16414 Duplicate IP
address detected
Critical Fault The PanelView has the same IP address
as another device on the EtherNet/IP
network.
Change the IP address of the PanelView
(on the Communication Setup screen) so
that is unique on the network.
16415 Unknown error
detected
Communication
Warning
An operating system message has
occurred.
Contact technical support.
16416 No network link Critical Fault Communications has not been
established with network.
Check Ethernet cable.
16417 DHCP/BootP
Enable failed
Communication
Warning
The DHCP/BootP Enable server failed to
allocate an IP address, subnet mask and
gateway address to the PanelView
terminal
Check DHCP/BootP Enable server on your
network.
16418 Invalid IP Address
or Subnet Mask
Communication
Warning
The IP address or the subnet mask of the
PanelView terminal is not valid.
Important: The Gateway Address cannot
be entered at the terminal; you must
configure this address in the
Communication Setup dialog of
PanelBuilder32.
Enter a valid IP address and/or the subnet
mask of the PanelView terminal on the
Communication Setup screen.
This error occurs if the downloaded
application has DHCP/BootP enabled and
it is then disabled at the terminal. On a
restart, the terminal will not have the
necessary information (IP Address,
Subnet Mask, Gateway Address) to
connect to the network.
16420 Invalid Gateway
Address
Communication
Warning
The Gateway Address is not valid. Change the Gateway Address in the
PanelBuilder32 software.
Error Number Terminal
Messages
Type Meaning Recommended Action