q Quality ST Quality of counter value
t TimeStamp ST Time of last counter change
pulsQty FLOAT32 CF Magnitude of the counted value 'per count' (value =
actVal x pulsQty)
1.5.8 Common Data Class: CMV_MAG_ANG_FLOAT
Description: Complex Measured value (w.r.t Floating Point Magnitude and Angle)
CDC Class: CMV
cVal Vector_MagnitudeAngle_Float MX Deadbanded complex measured
vector. Updated to the current
value of instCVal when the value
has changed according to the
configuration parameter db.
q Quality MX Quality of the measurement value
t TimeStamp MX Time deadbanded magnitude last
exceeded its db configuration
parameter
units Unit_Multiplier CF Unit of the attribute representing
the data
db INT32U CF Measurement deadband
rangeC RangeConfig_Deadband CF Measurement range configuration
attributes
1.5.9 Common Data Class: CMV_MAG_FLOAT
Description: Complex Measured value (w.r.t Floating Point Magnitude)
CDC Class: CMV
cVal Vector_Magnitude_Float MX Deadbanded complex measured vector.
Updated to the current value of instCVal
when the value has changed according
to the configuration parameter db.
q Quality MX Quality of the measurement value
t TimeStamp MX Time deadbanded magnitude last
exceeded its db configuration parameter
units Unit_Multiplier CF Unit of the attribute representing the data
db INT32U CF Measurement deadband
rangeC RangeConfig_Deadband CF Measurement range configuration
attributes
1.5.10 Common Data Class: DEL_SEG_ANG
Description: Phase to phase measurements for a 3-Phase system (w.r.t Phase
Seggregation + Angle)
CDC Class: DEL
phsAB CMV_MAG_ANG_FLOAT -- Measurement values for Phase A to
Phase B
phsBC CMV_MAG_ANG_FLOAT -- Measurement values for Phase B to
Phase C
phsCA CMV_MAG_ANG_FLOAT -- Measurement values for Phase C to
Phase A