1.5.23 Common Data Class: MV_FLOAT_D
Description: Measured value (w.r.t Floating Point Value with Description)
CDC Class: MV
mag AnalogueValue_Float MX Deadbanded magnitude of the
instantaneous value of a measured value
or harmonic value. Updated to the
current value of instMag when the value
has changed according to the
configuration parameter db.
q Quality MX Quality of the measurement value
t TimeStamp MX Time deadbanded magnitude last
exceeded its db configuration parameter
units Unit_Multiplier CF Unit of the attribute representing the data
db INT32U CF Measurement deadband
rangeC RangeConfig_Deadband CF Measurement range configuration
attributes
d VISIBLE_STRING255 D Description of the status element
1.5.24 Common Data Class: SEQ_MAG_ANG
Description: Sequence components of a measurement value (w.r.t Magnitudes + Angles)
CDC Class: SEQ
c1 CMV_MAG_ANG_FLOAT -- Sequence component 1 (For semantic
meaning see seqT)
c2 CMV_MAG_ANG_FLOAT -- Sequence component 2 (For semantic
meaning see seqT)
c3 CMV_MAG_ANG_FLOAT -- Sequence component 3 (For semantic
meaning see seqT)
seqT ENUMERATED8
(MMS Type: INT8)
MX seqT Sequence quantity measurement type
(Pos-Neg-Zero or Dir-Quad-Zero)
1.5.25 Common Data Class: SPC_CONTROL_NS
Description: Controllable Single Point (NAME SPACE)
CDC Class: SPC
ctlVal BOOLEAN C Control value (Off - FALSE, On - TRUE)
bypass ENUMERATED8
(MMS Type: BSTR16)
C Bypass Bypass X
origin Originator ST Originator of the last change of the
controllable data
stVal BOOLEAN ST Status value of the data
q Quality ST Quality of the status value
t TimeStamp ST Timestamp of the last change in state of
status value
ctlModel ENUMERATED8
(MMS Type: INT8)
CF ctlModel Control model (Corresponding to the
behaviour of the data)
sboTimeout INT32U CF Select Before Operate timeout period (in
milliseconds)
cdcNs VISIBLE_STRING255 EX Common Data Class name space
cdcName VISIBLE_STRING255 EX Name of the Common Data Class