4.3 LED signalling circuits
The signalling circuits are made up of twelve LEDs (see fig. 3).
Four LEDs are strictly assigned to previously established signalling
correct feeder output voltage values
blinking light during setting change or test
correctly connected to the network; ON with blinking
when the device is provided with
keyboard, PC or network, can be:
- monostable operation; it immediately goes off when the
cause that made it go on is removed
- bistable operation (MEMOR): the LED remains on until a
from the front push-button, digital input or
serial connection. Any failure of auxiliary voltage entails the
momentary loss of the luminous signals, which are reset as
soon as the voltage is restored.
A pocket is provided close to the LEDs, where explanatory la
If duly programmed from the keyboard, PC or
the five optoinsulated inputs can be assigned to
s referring to the device.
The factory settings envisage that the
above mentioned functions
The input voltage can differ from the auxiliary voltage of the
The enabling of the digital inputs
can be programmed by normally
the digital inputs associated with the Start LB
and Start DB functions must be ON on front , whereas all the
Each type of tripping is associated with a partial or total counter
The counters work within the 0-9999 range; if
the counter is automatically set to zero and the counting restarts
All the partial counters can be set to zero from the keyboard, from
When an event occurs, the following information is stored in
time, minute, second and thousandth of a
second concerning the tripping moment
- number of parallel attempts
All this information is called 'event'.
The circulating memory allows the last eight events to
and when this number is excee
older: the last event is sto
The stored events can be read from the front display unit or from
a PC serially connected to the
Furthermore, the device can store
(with relative date and time) and make them readable through PC
The device can display the
effective current values concerning
the bar voltage expressed in Ubn multiples, the generator voltage
phase difference expressed in grades.
It also displays the effective current primary values relative to the
bar and generator voltage expres
Besides the normal diagnostics already dealt with, the device
also offers, in the TEST mode, the possibility of testing the
the display and the output relays.
display unit (LCD) for two seconds.
Once the test is over, the LEDs that were supposed to be ON
before the test remain ON and the display unit goes back to the
previous information displayed; the test can be carried out
during any running condition, without affecting the operation in
and checked for correct oper
this way, any external signalling or control circuit can be
s energized for 150 and 200 ms.
If commands are already present, the
message appears on the display unit.
The test on auxiliary relays does not affect counters, event