EasyManua.ls Logo

Alstom MX3EG1A - 3.3 Frequency regulator; 3.4 Load pulse and parallel command; 3.5 Dead-bar mode

Alstom MX3EG1A
38 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
pag. 8
MDE/A133 2295 001
MX3EG1A
3.4 Load pulse and parallel command
When none of the following thresholds: DUb, DUg, DU, Dfb, Dfg,
Df, Dp is
tripping, the protection sends a parallel command with
a pulse duration equal to tc; the command is sent with a n
advance time equal to tr (breaker trip time) compared to the
expected Dp=0 phase difference instant: this to
allow the breaker
to be closed just when the voltages are in phase with each other.
If after the twc time the breaker is not closed (corresponding
digital input enabling failed) and the parallel conditions are still
acceptable, a further closing comma
nd is sent; the max. number
of commands is defined by the set Ns.
If after the last attempt the breaker is not closed, the 'failed
synchronization sequen
ce' command - once the max. number of
attempts has been reached - as well as any signal corresponding
to the event will be sent; the partial and total counter relative to the
event is incremented and the event logging is enabl
ed.
In the same way,
if the sequence has not
been terminated after
the max. tim
e ts defined
for
the parallel
sequence,
the 'failed
synchronization sequence' command - following a timeout
condition - as well as any signal corresponding to the event will
be
sent; the partial and total counter relative to the mentioned event
is incremented and the event logging is enabled.
On receiving the
'breaker closed' signal, the 'correctly-performed
synchronizat
ion sequence' command is
sent, the event logging
is also enabled.
Together with the 'breaker closing' command, in the event of LP
load pulse in ON
mode, a frequency increase pulse is issued for
a
time duration equal to tlp. This frequency increase pulse and,
therefore, the system
speed are
aimed at
preventing
energy
returns from occurring.
3.5 Dead-bar mode
The device can even be used to feed an out-of-voltag
e bar (dead
bar):
the generator parameter can
be set before
the breaker
closing.
The sequence start occurs upon enabling the digital input
associated with a DB start (with enabling characteristic on
front).
The dead-bar level is defined by the Ud set value; below the said
value the bar is considered as not-fed.
3.5.1 DB
dead-bar mode
OFF
Any request of dead-bar synchronization is ignored.
3.5.2 DB
dead-bar mode
ON
The device checks
that the generator frequenc
y and voltage lie
within the limits defined by Dfg
and DUg, by controlling the parallel
breaker closing without carrying out any adjusting action.
3.3 Frequency regulator
3.3.1
Max. deviation ra
ted frequency/ bar
frequency
The device works by comparing the fb bar frequency with the fn
rated frequency.
When the deviation between the two frequencies exceeds theDfb
set value, the 'START reques
t failed' command - due to
fb out-
of-tolerance condition - as well as
any signal corresponding to the
event are sen
t;
the partial a
nd total coun
ter relative t
o the
mentioned event is incremented and the
event logging is enabled.
3.3.2
Max. deviation rate
d frequency/ generator frequency
The device works comparing the fg generator frequency with the
rated frequency.
When the deviation between the two frequencies exceeds the Dfg
set value, the 'START reques
t failed' command
- due to fg out-
of-tolerance condition - as well as
any signal corresponding to the
event, are sent; the partial and total counter relative to the event
is incremented and the event logging is enabled.
3.3.3 Max. frequency difference
The device works by comparing the fb bar frequency with the fg
generator frequency.
When the difference between the
two frequencies exceed the
Df
set value, the 'frequency increase' (if fg<fb) or 'frequency decrease'
(if fg>fb) command is sent.
The frequency increase/decrease commands can be of
'continuous' or 'pulse' type depending on the
regulation mode that
has been set, that is CPf CONT or PULSE.
If the PULSE
mode has been set, the pulse time is defined by the
tfpu set parameter; the min. pulse interval is given by the tfpa set
parameter.
If the phase difference between bar and generator constantly
lies
above the Dp set threshold,
after a time interval equal to tfpm has
expired
since the last frequency increase/d
ecrease command,
the following types of desynchronization commands will be sent:
'frequency increase' in the event of SUPERSYNC live
bar parallel
mode or 'frequency decrease' in the
event of SUBSYNClive bar
parallel mode; in case of NORM live bar parallel mode the
'increase' comman
d will be sent when the generator is in 'delay'
condition compared to the bar, whereas the 'decrease' command
will be sent when
the generator is in 'advance' condition.