EasyManuals Logo

Amana APG M Series User Manual

Amana APG M Series
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #18 background imageLoading...
Page #18 background image
18
2. With the unit operating, time the smallest dial on the
meter for one complete revolution. If this is a 2 cubic
foot dial, divide the seconds by 2; if it is a 1 cubic foot
dial, use the seconds as is. This gives the seconds
per cubic foot of gas being delivered to the unit.
3. ,1387 *$6+7*9$/8([6(&3(5&8%,&
FOOT
EXAMPLE: Natural gas with a heating value of 1000 BTU
per cubic foot and 34 seconds per cubic foot as determined
E\6WHSWKHQ
Input = 1000 x 3600 / 34 = 106,000 BTU per Hour.
127(%78උ඗ඖගඍඖග඗ඎගඐඍඏඉඛඛඐ඗ඝඔඌඊඍ඗ඊගඉඑඖඍඌ
ඎක඗ඕගඐඍඏඉඛඛඝ඘඘ඔඑඍක7ඐඑඛඕඍඉඛඝකඍඌඑඖ඘ඝගඕඝඛග
ඖ඗ගඊඍඏකඍගඍකගඐඉඖඛඐ඗ඟඖ඗ඖගඐඍඝඖඑගකඉගඑඖඏ඘ඔඉගඍ
4. 5HOLJKWDOORWKHUDSSOLDQFHVWXUQHGRႇLQVWHS%H
sure all pilot burners are operating.
Main Burner Flame Check
)ODPHVVKRXOGEHVWDEOHVRIWDQGEOXHGXVWPD\FDXVH
RUDQJHWLSVEXWWKH\PXVWQRWEH\HOORZDQGH[WHQGLQJ
GLUHFWO\RXWZDUGIURPWKHEXUQHUZLWKRXWFXUOLQJÀRDWLQJRU
OLIWLQJRႇ
7ඍඕ඘ඍකඉගඝකඍ5එඛඍ&ඐඍඋඓ
Check the temperature rise through the unit by placing
thermometers in supply and return air registers as close
to the unit as possible. Thermometers must not be able to
sample temperature directly from the unit heat exchangers,
or false readings could be obtained.
ng
&ඐඍඋඓඑඖඏ7ඍඕ඘ඍකඉගඝකඍ5එඛඍ
1. All registers must be open; all duct dampers must be
LQWKHLU¿QDOIXOO\RUSDUWLDOO\RSHQSRVLWLRQDQGWKH
unit operated for 15 minutes before taking readings.
2. The temperature rise must be within the range speci-
¿HGRQWKHUDWLQJSODWH
127($එකගඍඕ඘ඍකඝකඍකඑඛඍඑඛගඐඍගඍඕ඘ඍකඝකඍ
ඌඑඎඎඍකඍඖඋඍඊඍඟඍඍඖඛඝ඘඘ඔඡඉඖඌකඍගඝකඖඉඑක
With a properly designed system, the proper amount of
temperature rise will normally be obtained when the unit
is operated at rated input with the recommended blower
speed.
If the correct amount of temperature rise is not obtained,
it may be necessary to change the blower speed. A high-
er blower speed will lower the temperature rise. A slower
blower speed will increase the temperature rise.
127(%ඔ඗ඟඍකඛ඘ඍඍඌ0867ඊඍඛඍගග඗ඏඑඞඍගඐඍ
උ඗කකඍඋගඉඑකගඍඕ඘ඍකගඝකඍකඑඛඍගඐක඗ඝඏඐගඐඍඝඖඑගඉඛ
ඕඉකඓඍඌ඗ඖගඐඍකගඑඖඏ඘ඔඉගඍ
(චගඍකඖඉඔ6ගගඑඋ3කඍඛඛඝකඍ&ඐඍඋඓ
The total external static pressure must be checked on this
XQLWWRGHWHUPLQHLIWKHDLUÀRZLVSURSHU
Total External Static Testing
1. Using a digital manometer measure the static pres-
VXUHRIWKHUHWXUQGXFWDWWKHLQOHWRIWKHXQLW1HJDWLYH
3UHVVXUH
.
Mode
.
7඗ගඉඔ(චගඍකඖඉඔ6ගගඑඋ
2. 0HDVXUHWKHVWDWLFSUHVVXUHRIWKHVXSSO\GXFW3RVL-
WLYH0HDVXUH
3. Add the two readings together.
127(%඗ගඐකඍඌඑඖඏඛඕඡඊඍගඉඓඍඖඛඑඕඝඔගඉඖඍ඗ඝඛඔඡ
ඉඖඌකඉඌඌඑකඍඋගඔඡ඗ඖගඐඍඕඉඖ඗ඕඍගඍකඑඎඛ඗ඌඍඛඑකඍඌ
4. Consult proper table for quantity of air.
If the external static pressure exceeds the minimum or
maximum allowable statics. Check for closed dampers,
GLUW\¿OWHUVXQGHUVL]HGRUSRRUO\ODLGRXWGXFWZRUN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Amana APG M Series and is the answer not in the manual?

Amana APG M Series Specifications

General IconGeneral
BrandAmana
ModelAPG M Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals