11.1 No Electric Heat Installed
If no electric heat accessory kit is installed, a cover plate
must be installed over the opening for electric heat. This
cover plate kit is available from Goodman
®
and Amana
®
brand distributors.
3 5 6 8 10 15 19/20 25
800 12 19 23 31 37
1000 9 15 19 25 30 44
1200 8 12 15 21 25 37 49 62
1400 7 11 13 18 21 32 42 53
1600 6 9 12 15 19 28 37 46
1800 5 8 10 14 16 25 33 41
2000 5 7 9 12 15 22 30 37
CFM
HEAT KIT NOMINAL kW
230/1/60 SUPPLY VOLTAGE - TEMP. RISE °F
Table 3
3568101519/2025
800
11 18 22 30 35
1000
9 1418242842
1200
7 1215202435 47 59
1400
6 1013172030 40 51
1600
6 9 11 15 18 27 35 44
1800
5 8 10 13 16 24 31 39
2000
4 7 9 12 14 21 28 35
CFM
HEAT KIT NOMINAL kW
220/1/60 SUPPLY VOLTAGE - TEMP. RISE °F
Table 4
3 5 6 8 10 15 19/20 25
800
10 17 21 28 33
1000
8 1317222740
1200
7 11141922334556
1400
6 10121619293848
1600
5 8 10 14 17 25 33 42
1800
5 7 9 12 15 22 30 37
2000
4 7 8 11 13 20 27 33
CFM
HEAT KIT NOMINAL kW
208/1/60 SUPPLY VOLTAGE - TEMP. RISE °F
Table 5
3 5 6 8 1015192021 or 25
AVPTC24B14
550 650 700 800 850 NR NR NR NR
AVPTC30B14
600 700 750 875 950 NR NR NR NR
AVPTC36C14
NR 850 900 1000 1200 1440 1500 1500 NR
AVPTC48C14
NR 850 900 1000 1200 1440 1500 1500 NR
AVPTC42D14
850** 1250 1300 1500 1550 1720 NR 1800 NR
AVPTC48D14
††
NR 1250 1300 1500 1550 1720 NR 1815 1850
AVPTC60D14
†††
NR 1250 1300 1500 1550 1780 NR 1850 1850
MINIMUM CFM REQUIRED FOR HEATER KITS
Heater Kit (Kw)
Please refer to page 16 for specific heater kit application guidelines.
Table 6
12 Electrical and Control Wiring
IMPORTANT: All routing of electrical wiring must be made
through provided electrical knockouts. Do not cut, puncture
or alter the cabinet for electrical wiring.
12.1 Building Electrical Service Inspection
This unit is designed for single-phase electrical supply
only. DO NOT OPERATE ON A THREE-PHASE
POWER SUPPLY. Measure the power supply to the
unit. The supply voltage must be measured and be in
agreement with the unit nameplate power requirements
and within the range shown.
Nominal Input Minimum Voltage Maximum Voltage
208 - 240 197 253
ELECTRICAL VOLTAGE
Table 7
12.2 Wire Sizing
Wire size is important to the operation of your equip-
ment. Use the following check list when selecting the
appropriate wire size for your unit.
FIRE HAZARD!
To avoid the risk of property damage, personal injury
or fire, use only copper conductors.
HIGH VOLTAGE!
Failure to do so may cause property damage,
personal injury or death.
Disconnect ALL power before servicing.
Multiple power sources may be present.
HIGH VOLTAGE!
To avoid property damage, personal injury or death
due to electrical shock, this unit MUST have an
electrical ground. The
electrical ground circuit may consist of an
appropriately sized electrical wire connecting the
ground lug in the unit control box to the building
electrical service panel.
Other methods of grounding are permitted if performed
in accordance with the National Electric Code
(NEC)/American National Standards Institute
(ANSI)/National Fire Protection Association (NFPA) 70
and local/state codes. In Canada, electrical grounding
is to be in accordance with the Canadian Electric Code
(CSA) C22.1.
uninterrupted, unbroken
Wire used must carry the Minimum Circuit Ampac-
ity (MCA) listed on the unit’s Series and Rating
Plate.