SERVICING
64
A DVANCED U SER M ENUS
SUBMENU ITEM USER MODIFIABLE OPTIONS COMMENTS
CL Reset YES or NO Selecting to default factory setting.
Cool Airflow Trim Hi (C TR H) -15% to +15% in 3% increments Selects the cooling airflow trim amount.
Cool Airflow Trim Int (C TR I) -15% to +15% in 3% increments Selects the cooling airflow trim amount.
Cool Airflow Trim Low (C TR L) -15% to +15% in 3% increments Selects the cooling airflow trim amount.
Cool Airflow Profile A, B, C, or D Selects the cooling airflow profile.
Cool ON Delay 5, 10, 20, 30 seconds Selects the indoor blower ON delay.
Cool OFF Delay 30, 60, 90, 120 seconds Selects the indoor blower OFF delay.
Dehumidification Select ON or OFF Selecting OFF disables dehumidification; selecting
ON enables dehumidification.
SUBMENU ITEM USER MODIFIABLE OPTIONS COMMENTS
Maximum Compressor RPS Range for Cooling
(COOL RPS RANGE)
Five different compressor RPS
ranges will be provided.
Select the appropriate range for the installed system
configuration.
Maximum Compressor RPS Selection for Cooling
(COOL RPS SELECT)
Ten compressor RPS values will be
provided within the range selected
in the COOL RPS RANGE menu
Select the appropriate compressor RPS for the
installed system configuration.
SUBMENU ITEM USER MODIFIABLE OPTIONS COMMENTS
HT Reset YES or NO Selecting to default factory setting.
Heat Airflow Trim Hi (H TR H) -15% to +15% in 3% increments Selects the Heating airflow trim amount.
Heat Airflow Trim Int (H TR I) -15% to +15% in 3% increments Selects the Heating airflow trim amount.
Heat Airflow Trim Low (H TR L) -15% to +15% in 3% increments Selects the Heating airflow trim amount.
Heat ON Delay 5, 10, 15 seconds Selects the indoor blower ON delay.
Heat OFF Delay 30, 50, 70, 90 seconds Selects the indoor blower OFF delay.
Maximum Defrost Interval 30 min., 1hr., 1.5hrs. and 2hrs. Selects time defrost interval
SUBMENU ITEM USER MODIFIABLE OPTIONS COMMENTS
Maximum Compressor RPS Range for Heating
(HEAT RPS RANGE)
Five different compressor RPS
ranges will be provided.
Select the appropriate range for the installed system
configuration.
Maximum Compressor RPS Selection for Heating
(HEAT RPS SELECT)
Ten compressor RPS values will be
provided within the range selected
in the HEAT RPS RANGE menu
Select the appropriate compressor RPS for the
installed system configuration.
COOL SETUP
HEAT SETUP
SET HEATING RUN VALUES (HT RUN VALUES)
SET COOLING RUN VALUES (CL RUN VALUES)