30 05/18/2021
Manual Stopstatus.
53. BID AMP HOURS
If a connected battery is equipped with a Battery I.D.
module, the battery amp-hour size (0000-9999) may
be reprogrammed into the BID. The control must be
in Manual Stopstatus.
54. BID BATTERY TYPE
If a connected battery is equipped with a Battery I.D.
module, the battery type may be programmed into
the BID. The control must be in Manual Stopsta-
tus.
00 FLD Flooded Lead Acid
01 CTM Custom curve (programmable)
02 YGR Sealed battery curve
03 SLR Sealed battery curve
04 DSG Sealed battery curve
05 SLE Sealed battery curve
06 DAG Sealed battery curve
07 CDR Sealed battery curve
08 MAX Opportunity Charge curve
55. PASSWORD
Optional password required to program if turned on.
56. NO GASSING HOURS
The number of Hours before the charger can begin
the gassing portion of the charging cycle. (0 – 8
Hours)
57. MAX BATT TEMP
The maximum battery temperature for charging to
start or continue. Once interrupted, the charge will
restart after the temperature drops 5 degrees F.
(For use with BID only)
58. BID START AMPS
Programs the charger start rate at the programmed
BID AH rating to the selected amps/100AH. For
example, to charge an 800AH battery at 320 amps,
the BID Start Ampswould be programmed to
40A/100AH. Please note that if the programmed rate
exceeds the maximum rated charger amps, the
charger output will be limited to the maximum current
rating.
59. BATTERY CHARGE AMP HOURS
The accumulated amp hours charged into the battery.
An Amp Hour Accumulator and BID module assembly
must be installed on the battery to use this function.
The Amp Hour Accumulator continually records this
data while it is installed on the battery.
The data is automatically read from the bid when the
control terminates each charge cycle, except for
Manual Stop. The data is stamped with the date and
BID number.
60. BATTERY DISCHARGE AMP HOURS
The accumulated amp hours discharged from the
battery. An Amp Hour Accumulator and BID module
assembly must be installed on the battery to use this
function. The Amp Hour Accumulator / BID continually
records this data while it is installed on the battery.
The data is automatically read from the bid when the
control terminates each charge cycle, except for
Manual Stop. The data is stamped with the date and
BID number.
61. LONG TERM AVERAGE BATTERY
TEMPERATURE
The average BID temperature of the battery. An Amp
Hour Accumulator and BID module assembly must be
installed on the battery to use this function. The BID
continually updates the average while it is installed on
the battery.
The data is automatically read from the bid when the
control terminates each charge cycle, except for
Manual Stop. The data is stamped with the date and
BID number.
62. BATTERY CYCLES
The number of battery discharge cycles, based on
the total discharge amp hours and 80% of the BID
amp hour setting. An Amp Hour Accumulator and
BID module assembly must be installed on the
battery to use this function. The control continually
updates this calculation using the total accumulated
discharge amp hours read in from the BID.
193111-121
EC2000 CONTROL FEATURES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ametek ECLIPSE II PLUS and is the answer not in the manual?

Ametek ECLIPSE II PLUS Specifications

General IconGeneral
BrandAmetek
ModelECLIPSE II PLUS
CategoryBattery Charger
LanguageEnglish

Related product manuals