A01-00159 Rev B
23
13: Maximum charger current setting
Interface
Setting
Parameter 2:
Set up the charger maximum
current.
For low voltage model with 24/36/48VDC
1/2/4/6/8: setting the charger maximum
current 1/2/4/6/8 in Ampere. (Default: 2A)
For high voltage model with 24/36/48VDC
1/2/4/6/8/10/12: setting the charger maximum
current 1/2/4/6/8/10/12 in Ampere. (Default:
2A)
For low voltage and high voltage model with
72/96VDC
1/2/4/6/8: setting the charger maximum
current 1/2/4/6/8 in Ampere. (Default: 2A)
Note: Please set the appropriate charger
current based on battery capacity used. The
recommended charging current is 0.1C~0.3C
of battery capacity as following table for
reference.
Battery capacity Total charging
(AH) current (A)
7~20
2
20~40
4
40~60
6
60~80
8
80~100
10
100~150 12
14: Charger boost voltage setting
Interface
Setting
Parameter 2: Set up the charger boost
voltage.
2.25-2.40: setting the charger boost voltage
from 2.25 V/cell to 2.40V/cell. (Default: 2.36V/
cell)