A01-00159 Rev B
33
6.0 SPECIFICATIONS
Tower Models
MODEL
ACDEF2000-11T
ACDEF3000-11T
CAPACITY*
2000VA/1850W
3000VA / 2740W
INPUT
Voltage
Range
Low Line
Transfer
160VAC/140VAC/120VAC/110VAC ± 5 % or
80VAC/70VAC/60VAC/55VAC ± 5 %
(Based on load percentage 100% - 80 % / 80 % - 70 %
/ 70 - 60 % / 60 % - 0)
Low Line
Comeback
175VAC/155VAC/135VAC/125VAC ± 5 % or
87VAC/77VAC/67VAC/62VAC ± 5 %
High Line
Transfer
150 VAC ± 5 %
High Line
Comeback
145 VAC ± 5 %
Frequency Range
40Hz ~ 70 Hz
Phase
Single phase with ground
Power Factor
0.95 @ full load
THDi
5% @ 100~130VAC
THDU < 1.6% @ input and full linear load condition
OUTPUT
Output voltage
100/110/115/120/127 VAC
AC Voltage Regulation
± 1% (Batt. Mode)
Frequency Range
(Synchronized Range)
47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz (Batt. Mode)
Current Crest Ratio
3:1
Harmonic Distortion
2 % THD (Linear Load); 4 % THD (Non-linear Load)