EasyManua.ls Logo

Amprobe AT-6000 - Special Applications; GFCI-Protected Circuit Wire Tracing; Finding Breaks;Opens

Amprobe AT-6000
33 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18
4.1 GFCI-Protected Circuit Wire Tracing: Connecting the AT-6000-T Transmitter to
GFCI Protected Circuits
Connecting the Transmitter to an Energized GFCI protected circuit using a separate ground
method will trip the GFCI protection. Use the following methods to work with GFCI
protected circuits. For a De-energized GFCI-protected outlet that is not tripped, you can
connect test leads directly to the outlet contacts using the De-energized Tip Sensor mode.
Method 1 – Bypass the GFCI circuitry to avoid tripping GFCI:
(for Energized GFCI-protected outlets only)
Remove the protective receptacle wall plate.
Using the alligator clip, attach the red test lead to the screw to connect the Energized
hot wire to the receptacle.
Connect the green test lead using a separate ground method.
Perform tracing as described in the Quick Scan or Precision Tracing sections.
Method 2 – Do NOT use separate ground to avoid tripping GFCI:
(for GFCI-protected outlets and breakers)
Connect the Transmitter with the test leads to the Neutral and Hot wires.
Perform tracing as described in one of the following modes: Quick Scan, Precision
Tracing or Breaker Locating.
Note: This type of connection causes signal coupling and reduces signal strength. If the
signal is too weak or untraceable, use Method 3.
Method 3 - De-energize the circuit:
(for GFCI-protected breakers)
Connect the Transmitter directly to the wire as described in wire tracing modes (Quick
Scan and Precision).
Perform tracing as described in one of the following modes: Quick Scan, Precision
Tracing or Breaker Locating.
4.2 Finding Breaks/Opens
It is possible to pinpoint the exact location where a wire is broken using the Precision
Tracing mode, even if the wire is located behind walls, floors or ceilings.
1. Make sure that wire is De-energized.
2. Use the steps described in the Precision Tracing mode to connect the Transmitter and
perform tracing.
3. For best results, ground all De-energized wires that run in parallel with the black test lead.
4. SPECIAL APPLICATIONS
Figure 4.2: Locating a break or open
www.calcert.com sales@calcert.com1.800.544.2843
0
5
10
15
20
25
30

Related product manuals