Technical Data
Voltage Test
Nominal voltage range ....12...690 V AC/DC
LED display row ................±12, ±24, 50, 120,
230, 400, 690 V
Tolerance ..........................in accordance with
EN 61243-3,
DIN VDE 0682-401
LC display (VP-720 only)....12–690 V AC/DC
LC display resolution
(VP-720 only) ....................1V
Tolerance of the
LC display (VP-720 only)....± (3 % of measured
value +3 digit)
Frequency range ..............DC, 40–70 Hz
Vibration function
(VP-720 only) ....................from approx. 150 V
when both pushbut-
tons are pressed
Voltage detection ............automatic
Polarity detection..............entire range
Internal basic load ............approx. 2.4 W
at 690 V
Test current........................< 3.5 mA at 690 V (do
not press buttons)
Connectable load..............approx. 140 W
at 690 V
(with time limit)
Test current load ..............< 200 mA
(press buttons)
Duty cycle (ED) ..................30 s
Recovery time....................240 s
Auto-Power-On ................> 12 V AC/DC
(press buttons)
> 24 V AC/DC (do
not press buttons)
Single-pole phase test (VP-710, VP-720 only)
Voltage range ..................100…690 V AC
against earth
Frequency range ..............40…70 Hz
Continuity test (VP-710, VP-720 only)
Switching threshold..........approx. 500 kΩ
Tolerance ..........................-0 %–+50 %
(in accordance with
IEC61243-3)
Test current ......................<5 µA
Overvoltage protection ....690 V AC/DC
Rotary field detection
Voltage range ..................100…400 V AC
against earth
Frequency range ..............40…70 Hz
Power supply
Power supply (VP-700)......from test object
Power supply
(VP-710, VP-720 only)........2 x batteries 1.5 V
micro IEC LR03
Power input
(from battery)....................max. 30 mA/
approx. 250 mW
22