UL COPYRIGHTED MATERIAL –
NOT AUTHORIZED FOR FURTHER REPRODUCTION OR
DISTRIBUTION WITHOUT PERMISSION FROM UL
SA10 Receptacles
Section SA10 effective April 13, 1993
SA10.1 An attachment plug receptacle shall not be employed in a marine converter or inverter intended
for use in an area in which ignition-protected equipment is required.
SA11 Arcing Parts
Section SA11 effective April 13, 1993
SA11.1 A component that can produce an arc, such as a snap switch or a relay, shall not be employed
in a marine converter intended for use in an area in which ignition-protected equipment is required, and
shall be marked in accordance with SA25.5.
Exception: A component that complies with the ignition protection test in Section SA21 need not comply
with this requirement.
SA12 Electrical Components
Section SA12 effective April 13, 1993
SA12.1 A component such as a resistor, a transformer, a solid-state device, and the like, that exceeds
150°C (302°F) during normal operation of the marine converter or inverter, shall comply with the
requirements for ignition-protection test in Section SA21.
PERFORMANCE
SA13 General
Section SA13 effective April 13, 1993
SA13.1 A representative sample of a marine converter or inverter shall be subjected to the
output-voltage-control, vibration, shock, and ignition-protection tests described in Sections SA14 – SA21.
Exception: Marine converters or inverters marked in accordance with SA25.7 are not subjected to the
tests described in Sections SA14 and SA15.
SA13A Water Spray Test
SA13A.1 After being subjected to the water spray test as described in SA13A.2 – SA13A.4, a marine
converter or inverter intended for open cockpit or weather deck mounting shall have no water within its
enclosure at a level higher than the lowest live part.
SA13A.1 added January 27, 1995
SA13A.2 The water spray test apparatus is to consist of three spray heads constructed in accordance
with the details shown in Figure SA13A.1 and mounted in a water-supply pipe rack as shown in Figure
SA13A.2. The water pressure is to be maintained at 5 lb per square inch (34 Kpa) at each spray head.
The distance between the center nozzle and the converter or inverter is to be approximately 5 feet (1.5
m). The marine converter or inverter is to be brought into the focal area of the three spray heads in such
a position and under such conditions as are most likely to result in entrance of water into the marine
OCTOBER 15, 2004UL 458SA6