UL COPYRIGHTED MATERIAL –
NOT AUTHORIZED FOR FURTHER REPRODUCTION OR
DISTRIBUTION WITHOUT PERMISSION FROM UL
27.2 A resistor, capacitor, inductor, or other part that is mounted on a printed-circuit board to form a
printed-circuit assembly shall be secured so that it cannot be displaced to result in a risk of electric shock
or fire by a force likely to be exerted on it during assembly, normal operation, or servicing of the converter
or inverter.
27.2 effective April 13, 1993
27.3 Consideration is to be given to a barrier or partition that is part of the converter assembly and that
provides mechanical protection and electrical insulation for a component connected to a printed-circuit
board.
28 Spacings
28.1 General
28.1.1 General environment spacings shall be as specified in Table 28.1. Protected environment
spacings – see 7.1 – 7.5 – shall be as specified in Table 28.2. For the purpose of this requirement, a
general environment is considered to be an environment other than a protected environment.
Exception No. 1: Converters or inverters complying with the requirements in the Standard for Insulation
Coordination Including Clearances and Creepage Distances for Electrical Equipment, UL 840, may have
spacings less than that specified in Tables 28.1 and 28.2. See 28.1.2 and 28.1.3.
Exception No. 2: Spacings may be as provided in 28.2.1 if liners and barriers are used.
Exception No. 3: Spacings may be as provided in 28.1.2, between adjacent foils on printed wiring boards
provided with a conformal coating complying with the requirements in the Standard for Polymeric Materials
– Use in Electrical Equipment Evaluations, UL 746C. See 28.1.2.
Exception No. 4: On printed wiring boards having a flammability classification of 94V-0 and constructed
from a base material having a minimum Comparative Tracking Index (CTI) rating of 100 and 175 volts for
protected and general environments respectively, spacings (other than to ground, between primary and
secondary circuits, and at field wiring terminals) are not specified between traces of different potential
connected in the same circuit if the spacings comply with the requirements in Section 48, or an analysis
of the circuit indicates that no more than 12.5 milliamperes of current will flow between short-circuited
traces having reduced spacings.
Exception No. 5: For multilayer printed wiring boards, the minimum spacing between adjacent internal foils
of opposite polarity and between an internal foil and a plated-through hole is 1/32 inch. If these foils are
in circuit described in 13.3 – 13.9, no spacing is specified.
Exception No. 6: The spacing requirements in Tables 28.1 and 28.2 may not apply to inherent spacings
of a component such as a switch, lampholder, or a motor. Such spacings are to comply with the
requirements for the component in question if the spacings are less than the values specified in Tables
28.1 and 28.2. Spacings from such components to another component and to the enclosure shall comply
with the appropriate spacings specified in this Standard.
Exception No. 7: Spacings between adjacent terminals of a power switching semiconductor device
including the connection points of the terminals of the device are not specified.
28.1.1 effective April 13, 1993
DECEMBER 14, 1993 UL 458 37