EasyManua.ls Logo

ANSI UL 458 - Bonding Conductor; General; Leakage Current Test

Default Icon
138 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UL COPYRIGHTED MATERIAL
NOT AUTHORIZED FOR FURTHER REPRODUCTION OR
DISTRIBUTION WITHOUT PERMISSION FROM UL
30.2 Bonding conductor
30.2.1 Bonding shall be accomplished by metal-to-metal contact between parts or by a separate bonding
conductor as specified in 30.2.2 30.2.4.
30.2.2 A bonding conductor shall be copper, a copper alloy, or other acceptable material.
30.2.3 A splice shall not be employed in a bonding conductor.
30.2.4 A separate bonding conductor shall not be smaller than the conductors supplying a converter.
30.2.5 A separate bonding conductor for an inverter shall have an ampacity rating equal to the total
inverter output.
30.2.5 effective April 13, 1993
PERFORMANCE
31 General
31.1 A representative sample of a converter or inverter shall be subjected to the tests described in
Sections 32 52. Unless otherwise specified, all tests are to be conducted at not less than the rated
voltage of the converter or the highest of a rated voltage range, and an ambient temperature of 25°C at
rated frequency. See Table 31.1.
31.1 effective April 13, 1993
Table 31.1
Values of test voltages
Rated voltage Test voltage
110 115 120
Between 116 219 Rated voltage
220 230 240
31.2 The secondary current and voltage are to be measured by using an average-indicating meter.
31.3 Output-current measurements of either half-wave or full-wave rectifier circuits are to be based on the
average current reading.
32 Leakage Current Test
32.1 The leakage current of a cord-connected converter or inverter rated for a nominal 120-volt supply,
when tested in accordance with 32.2 32.6 shall not be more than 0.75 milliampere.
32.1 effective April 13, 1993
DECEMBER 14, 1993 UL 458 45

Table of Contents