UL COPYRIGHTED MATERIAL
NOT AUTHORIZED FOR FURTHER REPRODUCTION OR
DISTRIBUTION WITHOUT PERMISSION FROM UL
37.3.2 A converter or inverter is to be mounted in an enclosure consisting of four vertical side walls at
right angles to each other, and a horizontal top and base of 1/2-inch-thick plywood or soft pine with a
nominal thickness of 3/4 inch. The interior surfaces are to be painted flat black and the joints are to be
tight or sealed. The converter or inverter is to rest on the base with the walls and top in as intimate contact
with the converter or inverter as the configuration on the converter or inverter permits.
37.3.2 effective April 13, 1993
37.3.3 A converter or inverter intended for flush mounting is to be flush mounted on a vertical surface and
the recessed portions are to be enclosed in accordance with 37.3.2.
37.3.3 effective April 13, 1993
37.4 Maximum overload without trip
37.4.1 A converter or inverter is to be operated under the conditions described in 37.1.1 37.3.3 at the
maximum load it can carry without resulting in the protector required by 20.2.1 to open the circuit
ultimate trip current. During the test:
a) Transformer winding temperatures shall not exceed 140°C (284°F) for Class A insulation, or
165°C (329°F) for a Class B or F insulation, or 20°C above the value specified in Table 37.1 for
any other class of insulation.
b) The temperature of any component other than a transformer shall not exceed that specified in
Table 37.1 by more than 20°C (36°F).
c) A flush-wall mounted converter or inverter shall also comply with the temperature limits
specified in Table 38.1.
d) A fixed or stationary type unit shall not exceed the temperature limits specified in Table 38.1
by more than 20°C.
37.4.1 effective April 13, 1993
37.4.2 With reference to 37.4.1, readily accessible branch-circuit overcurrent-protective devices in a
secondary circuit shall be shunted during the test if they would open the circuit prior to the opening of an
internal protective device.
38 External Surface Temperature Limits Test
38.1 During the normal temperature test described in Section 37, Temperature Test, surface
temperatures shall not exceed the applicable values specified in Table 38.1. The results of a test that is
conducted at a room temperature of other than 25°C (77°F) is to be corrected to 25°C (77°F). See 37.1.8.
38.1 effective April 13, 1993
DECEMBER 14, 1993UL 45856