2.11 FLUSH-WALL-MOUNTED UNITS Units that are intended to be recessed in a wall.
2.11 effective April 13, 1993
2.12 LIMITED-ENERGY CIRCUIT A circuit having a voltage not exceeding 1000 volts and the energy
limited to 100 volt-amperes by a secondary winding of a transformer, or a fixed impedance.
2.12 effective April 13, 1993
2.13 LIVE PART Denotes metal or conductive parts that, during intended use, have a potential
difference with respect to ground or any other conductive part.
2.13 effective April 13, 1993
2.14 LOW-VOLTAGE, LIMITED ENERGY CIRCUIT A circuit involving an alternating voltage of not
more than 30 volts rms (42.4 volts peak) or a direct voltage of not more than 60 volts and supplied by:
a) An inherently limiting Class 2 transformer;
b) A non-inherently limiting Class 2 transformer and an overcurrent protective device that is:
1) Not of the automatic reclosing type;
2) Trip-free from the reclosing mechanism; and
3) Not readily interchangeable with a device of a different rating;
c) A combination of an isolated transformer secondary winding and a fixed impedance that
complies with all the performance requirements for an energy-limiting Class 2 transformer or
power source;
d) A dry-cell battery that is isolated from the primary circuit and having output characteristics no
greater than those of an energy-limiting Class 2 transformer or power source; or
e) A combination of a rechargeable battery and a fixed impedance that complies with all of the
performance requirements for an energy-limiting Class 2 transformer or power source.
2.14 effective April 13, 1993
2.15 PORTABLE POWER INVERTER A power inverter that has no provisions for permanent
mounting or wiring, and can be easily carried or conveyed by hand.
2.15 revised October 15, 2004
2.16 POWER-CONVERTER OR POWER-INVERTER SYSTEM An integral combination of a
converter or inverter, power-supply assembly, branch-circuit breakers, grounding bar, marking, and the
like, that are necessary for a complete installation.
2.16 effective April 13, 1993
2.17 POWER SUPPLY ASSEMBLY Conductors, including grounding conductors insulated from each
other, connectors, attachment plugs, and all other fittings, grommets, or devices installed for the
purpose of delivering energy from a source of supply to a power-converter or inverter system of a land
vehicle or marine craft.
2.17 effective April 13, 1993
OCTOBER 15, 2004 UL 458 9