9.6 Proportion adjustable (PCU) Debug Description
9.6.1Technical parameters
Input
—Input signal420mADC; 210VDC; 05VDC 010VDC; 15VDC
—Input resistance250Ω
—Feedback signal1010
Output
—Output signal450mADC
—Load resistance Max 750Ω
—Control outputRelay tip250VAC10AResistance load
ResolutionMin 1/1000
Adjustment of dead zone0.1%4.5%
Working temperature-1060
Relative humidityMax 90%Non-Condensed
Position transform precision±0.5%±1.5%
Dielectric Vol.Proof1500AC /minInput to output,Power supply to each
Shock or impactXYZ10g
10. Running Test
10.1 Manual Operation
Cut power before manual operation, turn the handwheel one circle, one side move the clutch handle in left
until occlude, continue to turn handwheel to decrease the opening (observe the opening by window glass).
10.2 Electric operation
Check the correspondence between the opening of actuator and valve by manual (full-open, full-closed) before
electric operation;
Check the wiring,
After confirming the above situation, start electric operation