EasyManua.ls Logo

APAR AR500 - Page 15

Default Icon
16 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15
Table 16.3. Response frame format for the READ function (minimum frame length - 7 bytes):
address of
the device
function
4 or 3
number of bytes in the
data field (max. 40*2=80
bytes)
data field - register value CRC check sum
1 byte
1 byte
1 byte
2
÷ 80
bytes (HB
-
LB)
2 bytes (LB
-
HB)
Example 16.3. Response frame for register value equal to 0: 0x01 - 0x04 - 0x02 - 0x0000 - 0xB930
Table 16.4. Response frame format for the WRITE function (frame length - 8 bytes):
copy of the claim frame for the WRITE function (Table 16.2)
Table 16.5. Special response (errors: function field = 0x84 or 0x83 in the case of the READ function and 0x86 in
the case of the WRITE function):
Error code
(HB-LB in the data field)
Error description
0x0001
non
-
existing register address
0x0002
wrong write register value
0x0003
improper function number
Example 16.5. Error frame for a non-existing read register address: 0x01 - 0x84 - 0x02 - 0x0001- 0x5130
Table 16.6. Map of registers for the MODBUS-RTU protocol
Register
address
HEX (DEC)
Value
(HEX or DEC)
Description of register and access type
(R- read only register, R/W - read and write register)
0x00 (0)
-1999 ÷ 19999 current measurement value
R/W
-1999 ÷ 9999
value to be displayed for the remote input (when parameter 0: inP = rEMo)
0x01 (1) 517 device type identifier R
0x02 (2)
100 ÷ 999 meter software (firmware) version
R
0x03 ÷ 0x05 0 not used or reserved
R
0x06 (6) 0 ÷ 1 current alarm status: bit0, bit0=1 means that the alarm is on
R
0x07 (7) 0 ÷ 20000 current state of the analog output (0 ÷ 20000 μA or 0 ÷ 10000 mV)
R
0x08 (8)
-100 ÷ 700 thermocouple cold tip temperature (resolution 0.1°C )
R
0x09 (9) -1999 ÷ 19999 minimum measurement value
R
0x0A (10) -1999 ÷ 19999 maximum measurement value
R
0x0B ÷ 0x10 0 not used or reserved
R
Configuration parameters (chapter 10)
0x11 (17) 0 ÷ 17
parameter 0: inP type of measurement input (chapter 10)
R/W
0x12 (18) 1 ÷ 20
parameter 1: FiLt digital filtration of measurements (response time)
R/W
0x13 (19) 0 ÷ 3
parameter 2: dot position of the point or resolution for temperature
R/W
0x14 (20) -1999 ÷ 18000
parameter 3: Lo1 lower limit for the alarm or bottom of the indication range
R/W
0x15 (21) -1999 ÷ 18000
parameter 4: Hi1 upper limit for the alarm or top of the indication range
R/W
0x16 (22) 0 ÷ 4
parameter 5: out1 alarm type
R/W
0x17 (23) -1999 ÷ 18000
parameter 6: SEt1 preset value for the alarm
R/W
0x18 (24) 0 ÷ 9999
parameter 7: H1 alarm hysteresis
R/W
0x19 (25) 0 ÷ 1
Parameter 8: AtYP type of analog output
R/W
0x1A (26) 0 ÷ 3
parameter 9: outA function of analog output
R/W
0x1B (27) -1999 ÷ 18000
parameter 10: A-Lo lower indication for retransmission
R/W
0x1C (28) -1999 ÷ 18000
parameter 11: A-Hi upper indication for retransmission
R/W