7.3. E-ITN 40 MOUNTING PLACE ON SEGMENTED AND PANEL RADIATORS
Place with suitable relation between the displayed value and the heat emission of the radiator over a
sufficiently operating range must be determined for allocator installation. Place of installation must be
determined according to the unified criteria in single billing (accounting) unit. E-ITN 40 installation must be
permanently protected against manipulation.
Warning: Failure to comply mounting procedure may result allocator malfunction!
7.3.1. Vertical position:
Install E-ITN 40 into 75% of the total radiator height (measured from bottom) – in relation to center of back
plate. If the height of the radiator is less than 400mm install allocator to 50 % of total height. Variations of the
mounting points height must not exceed ± 10 mm.
7.3.2. Horizontal position:
For both variants of vertical installation, place E-ITN 40 into the half of length L. In cause of odd number of
the spaces, place E-ITN 40 into the gap closer to the end of the radiator, i.e. at radiator with 10 segments
between 5. and 6. segment. On radiators with length L>2000 mm or radiators with excessive nominal output
install two E-ITN 40 placed in 25% of total radiator sized (measured from sides of radiator).