EasyManuals Logo

APC Smart-UPS VT Manual

APC Smart-UPS VT
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
990-2282A-001 Smart-UPS® VT 10-40 kVA 400V, 208V, 200V – Operation 7
Operation Procedures
How to turn into bypass
Single System – turning into internal bypass.
Caution
The load is not protected by the UPS and the power is not conditioned when the internal
mechanical bypass lever is activated.
Warning
In bypass operation the batteries are still charged. If a total power off is required, the batteries
must be pulled out to the red disconnect line, see the section How to perform a total power off.
Note
This procedure is not applicable to parallel systems as the internal mechanical bypass lever is
unavailable.
Note
If the UPS is running and controllable through the display, carry out steps 1 through 5. If not,
go directly to step 6.

Check that the UPS is in bypass. The green
(LOAD ON) and the yellow (BYPASS) LEDs
are lit.
Remove the Front Panel from the UPS (see
the Receiving and Unpacking sheet referred
to under the section Companion manuals).
Chrg 100%
Load 000%
xxxVin 000Vout x0Hz
Runtime: 0hr 0m
Press
Control
Status
Setup
Logging
Display
Diags
Help
Use
Press
UPS into Bypass
Do Self Test
Simulate Power Fail
Start Runtime Cal
Use
Press
Confirm:
UPS into Bypass
NO, ABORT
YES, UPS into Bypass
Use Press

Other manuals for APC Smart-UPS VT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the APC Smart-UPS VT and is the answer not in the manual?

APC Smart-UPS VT Specifications

General IconGeneral
Noise level55 dB
Output power24000 W
Input frequency40/70 Hz
Maximum current41 A
Output power capacity30 kVA
Emergency Power Off (EPO)Yes
Battery typeVRLA
Dimensions (WxDxH)559 x 813 x 1499 mm
Nominal input voltage400 V
CertificationC-tick, CE, EN 50091-2, EN/IEC 62040-3, IEC 61000-3-2, IEC 61000-3-3, ISO 14001, ISO 9001, VFI-SS-112
Product colorBlack
Battery recharge time5 h
Operating altitude0 - 999.9 m
Non-operating altitude0 - 15000 m
Storage temperature (T-T)-15 - 45 °C
Operating temperature (T-T)0 - 40 °C
Operating relative humidity (H-H)0 - 95 %
Harmonized System (HS) code85078000
Weight and Dimensions IconWeight and Dimensions
Weight629090 g
Package weight660000 g