Installation and Operation Manual
ECN: 003155
Date: 06/4/2013
48
AC-SmartStart-7608-Series_IOM Rev 04
LAN Module & Communications
optdUnitMode read-only Unit mode is local or remote: 1 = remote, 2 = local 1.1.1.1.2.20.0
optdUndervoltageSetpointA read-only Undervoltage dropout setpoint for channel A, units are Volts 1.1.1.1.2.21.0
optdUndervoltageSetpointB read-only Undervoltage dropout setpoint for channel B, units are Volts 1.1.1.1.2.22.0
ThrsVoltageHigh read-only Threshold voltage triggering overvoltage trap, units are volts x 10 1.1.1.1.3.1.0
ThrsVoltageLow read-only Threshold voltage triggering undervoltage trap, units are volts x 10 1.1.1.1.3.2.0
ThrsCurrentHigh read-only Threshold current triggering overcurrent trap, units are amps x 100 1.1.1.1.3.5.0
ThrsTemperatureHigh read-only Threshold temp triggering overtemp trap, units are degrees C x 10 1.1.1.1.3.13.0
ThrsLoginFail read-only Number of login failures triggering error 1.1.1.1.3.14.0
ThrsCommFail read-only Number of comm failures triggering error 1.1.1.1.3.15.0
circRemoteMessage1 read-only Remote message 1 text 1.1.1.1.4.1.0
circRemoteMessage1 read-only Remote message 1 text 1.1.1.1.4.1.0
circActive1 read-only Auxiliary contact circuit 1: 1 = inactive, 2 = active 1.1.1.1.4.3.0
circActive2 read-only Auxiliary contact circuit 2: 1 = inactive, 2 = active 1.1.1.1.4.4.0
circOpenCircuit read-only Circuit causing open-circuit trap: 0 = none, 1 = circuit 1, 2 = circuit 2 1.1.1.1.4.5.0
snmpTrapRecipient1 read-only IP address of trap recipient 1 1.1.1.1.5.1.0
snmpTrapRecipient2 read-only IP address of trap recipient 2 1.1.1.1.5.2.0
snmpTrapRecipient3 read-only IP address of trap recipient 3 1.1.1.1.5.3.0
smtpServerAddress read-only IP address of SMTP server 1.1.1.1.6.1.0
smtpHostID read-only Host.domain of e-mail sender 1.1.1.1.6.4.0
smtpFrom read-only E-mail address of the sender 1.1.1.1.6.5.0
smtpEmailRecipient1 read-only E-mail address of recipient 1 1.1.1.1.6.6.0
smtpEmailRecipient2 read-only E-mail address of recipient 2 1.1.1.1.6.7.0
smtpEmailRecipient3 read-only E-mail address of recipient 3 1.1.1.1.6.8.0
pingHost1 read-only IP address of host powered by outlet 1 1.1.1.1.7.1.0
pingHost2 read-only IP address of host powered by outlet 2 1.1.1.1.7.2.0
pingHost3 read-only IP address of host powered by outlet 3 1.1.1.1.7.3.0
pingHost4 read-only IP address of host powered by outlet 4 1.1.1.1.7.4.0
pingHost5 read-only IP address of host powered by outlet 5 1.1.1.1.7.5.0
pingHost6 read-only IP address of host powered by outlet 6 1.1.1.1.7.6.0
pingHost7 read-only IP address of host powered by outlet 7 1.1.1.1.7.7.0
pingHost8 read-only IP address of host powered by outlet 8 1.1.1.1.7.8.0
PingInterval read-only Interval between pings in sec. Zero disables the ping feature 1.1.1.1.7.9.0
pingTimeout read-only Time-out in milliseconds before ping attempt fails 1.1.1.1.7.10.0
pingFailThreshold read-only Number of failed pings before device is power-cycled 1.1.1.1.7.11.0
pingFailedHost read-only Most recently failed host 1.1.1.1.7.13.0
pingHostEnabled1 read-only Ping host enablement flag 1, 1 = disabled, 2 = enabled 1.1.1.1.7.14.0
pingHostEnabled2 read-only Ping host enablement flag 2, 1 = disabled, 2 = enabled 1.1.1.1.7.15.0
pingHostEnabled3 read-only Ping host enablement flag 3, 1 = disabled, 2 = enabled 1.1.1.1.7.16.0
pingHostEnabled4 read-only Ping host enablement flag 4, 1 = disabled, 2 = enabled 1.1.1.1.7.17.0
pingHostEnabled5 read-only Ping host enablement flag 5, 1 = disabled, 2 = enabled 1.1.1.1.7.18.0
pingHostEnabled6 read-only Ping host enablement flag 6, 1 = disabled, 2 = enabled 1.1.1.1.7.19.0
pingHostEnabled7 read-only Ping host enablement flag 7, 1 = disabled, 2 = enabled 1.1.1.1.7.20.0
pingHostEnabled8 read-only Ping host enablement flag 8, 1 = disabled, 2 = enabled 1.1.1.1.7.21.0
PingRestartDelay1 read-only Interval to wait before powering-on outlet 1 in seconds 1.1.1.1.7.22.0
PingRestartDelay2 read-only Interval to wait before powering-on outlet 2 in seconds 1.1.1.1.7.23.0
PingRestartDelay3 read-only Interval to wait before powering-on outlet 3 in seconds 1.1.1.1.7.24.0