Installation and Operation Manual
ECN: 003155
Date: 06/4/2013
28
AC-SmartStart-7608-Series_IOM Rev 04
Windows Conguration & Control Utility
There are two sets of external contacts on the rear connector of the PDU. Their
ratings are reviewed in the features and specification section of this manual. The
external contacts can be forced on or off by selecting the correct button or they can be
controlled by voltage, current, or temperature. The actuation level of the parameter is
set by the programmed values reviewed in the previous section “Alarm Settings”.
The unit has the capability of displaying a message based on an input on the auxiliary
connector located at the rear of the PDU. If there is a change in state on either of the
inputs, a message of “UFFW1” or “UFFW2” displays if the message function is enabled.
When used with the optional LAN module, an actual text message can be displayed or
e-mailed.
6.7 TROUBLESHOOTING PROGRAM SETUP
A common installation problem exists when the operating system will not allow the install
program to update the required system files. The symptom of this problem is either an
error message or a continuous reboot cycle.
Some causes could be:
Anti-Virus software.
You do not have computer administrator privileges.
The Operating System is blocking or protecting the system files.
Try these steps:
Disable any anti-Virus software.
See your network administrator if applicable.
Run the setup program after booting the computer in SAFE MODE