Installation and Operation Manual
ECN: 003155
Date: 06/4/2013
49
AC-SmartStart-7608-Series_IOM Rev 04
PingRestartDelay4 read-only Interval to wait before powering-on outlet 4 in seconds 1.1.1.1.7.25.0
PingRestartDelay5 read-only Interval to wait before powering-on outlet 5 in seconds 1.1.1.1.7.26.0
PingRestartDelay6 read-only Interval to wait before powering-on outlet 6 in seconds 1.1.1.1.7.27.0
PingRestartDelay7 read-only Interval to wait before powering-on outlet 7 in seconds 1.1.1.1.7.28.0
PingRestartDelay8 read-only Interval to wait before powering-on outlet 8 in seconds 1.1.1.1.7.29.0
unitName read-only Descriptive name of unit 1.1.1.1.8.1.0
unitLoginFailCount read-only Login failure count 1.1.1.1.8.2.0
unitCommFailCount read-only Communication failure count 1.1.1.1.8.3.0
LAN Module & Communications
7.9.2 SNMP Traps
SNMP traps are issued if trap recipients have been specified and any of the following
conditions occur:
• Line voltage A greater than or equal to high threshold
• Line voltage A less than or equal to low threshold
• Line voltage B greater than or equal to high threshold
• Line voltage B less than or equal to low threshold
• Load current A greater than or equal to high threshold
• Load current B greater than or equal to high threshold
• Temperature greater than or equal to high threshold
• Ping failure threshold exceeded for host
• Remote circuit opened
• Login failure, logins disabled
• Serial communications between the PDU and the LAN module failed
• Test only
7.9.3 SMTP (E-mail Alerts)
E-mails are issued if e-mail recipients have been specified and any of the following
conditions occur:
• Line voltage A greater than or equal to high threshold
• Line voltage A less than or equal to low threshold
• Line voltage B greater than or equal to high threshold
• Line voltage B less than or equal to low threshold
• Load current A greater than or equal to high threshold
• Load current B greater than or equal to high threshold
• Temperature greater than or equal to high threshold
• Ping failure threshold exceeded for host
• Remote circuit opened
• Login failure, logins disabled
• Serial communications between the PDU and the LAN module failed