AIR TO WATER POOL HEAT PUMP VERTICLE PH SERIES
26/ 52 VERSION 19 , RELEASE 29th June 2020
26
/
52
LA=3
Compressor
turn off ,
water pump
each
30mins start
3mins to
work.
LA=4
Compressor
turn off ,
water pump
each
30mins start
4mins to
work.
LA=N
Compressor
turn off ,
water pump
each
30mins start
N mins to
work.
LF
The protect temp of exhaust avoid too high
0-150
125
LO
The protect between water inlet and outlet temp too high
0-60
LO=0,
cancel this
protection
H1
Minimum defrost cycle (min)
20-99min
45
H2
Defrost start temperature setting
0-15
-2
H3
The maximum time set defrost
5-20min
10min
H4
Exit defrost temperature setting
1─40
20
H5
Enter defrost the deviation temp between ambient
temperature and coil temp 1 (more than ambient temp -6
deg.C)
0─60
5
H6
Allow defrost when ambient less than h6 selection
0─60
13
H7
Enter defrost the deviation temp between ambient
temperature and coil temp 1 (less than ambient temp -6
deg.C)
0─60
8
p3
Soft protection exhaust temperature
70135
90
F1
The number of online setting (Celsius / Fahrenheit
Conversion )
1-16 (0-1)
1(0)
F2
Time delay time on line number
20s-120s
60s