9.8.4 Electrical fast transient IEC255-22-4, BS 142-1.4.4, IEC 801-4
Auxiliary supply Class III 2kV
K-Bus communication port Class III 2 kV – capacitive coupling
IEC-870 Port None
9.8.5 Electrostatic discharge IEC 255-22-2, IEC 801-2
Class II 4kV – point contact discharge.
Note: The IEC-870 port will not withstand electrostatic discharges (air or
contact).
9.9 Environmental
9.9.1 Temperature IEC 68-2-1, BS 2011 Part 2.1A & IEC 68-2-2, BS 2011 Part 2.1B
Storage and transit: –25°C to +70°C
Operating: –25°C to +55°C
9.9.2 Humidity IEC68-2-3, BS 2011 Part 2.1 Ca
56 days at 93% relative humidity and +40°C
9.10 Mechanical tests
9.10.1 Vibration IEC 255-21-1 Class I
9.10.2 Shock and bump IEC 255-21-2 Class I
9.10.3 Seismic IEC 255-21-3 Class I
9.11 Enclosure protection IEC529 IP20
9.12 Battery
Replacement
See Section 11. Problem Solving.
Disposal
The battery should be removed from the unit and have any connection leads
removed before disposal, taking precautions to avoid short circuits. Particular
regulations within the country of operation may apply to the disposal of lithium
batteries.