P92x/EN CT/E11 Technical Guide
Modbus Protocol
Page 14/118 MiCOM P921-P922-P923
1.7.2 Page 0 : Product information, remote signalling and remote measurements
Read only access
Address Group Description
Settings
range
Step Unit Format
Default
settings
0000 Product
information
Description of the relay
characters 1 and 2
- F10
0001 Description of the relay
characters 3 and 4
-F10P9
0002 Description of the relay
characters 5 and 6
- F10 21 or 22 or
23
0003 Factory reference
characters 1 and 2
-F10AL
0004 Factory reference
characters 3 and 4
-F10ST
0005 Software version 10 - xx 1 - F21
0006 Communication type 0-2 1 - F41
0007 Internal ratio :
numerator
F1
0008 Internal ratio :
denominator
F1
0009 Start information
(VDEW)
F24
000A to
000C
Reserved
000D Active configuration
group
1-2 F1
000E Setting mode 0-1 1 - F24 0
000F Status of the protection F45
0010 Remote
signalling
Logic input 0 to 3 or 31 1 - F12
0011 Logic data 0 to 03FF 2
n
-F20
0012 Internal logics 0 to FFFF 2
n
-F22
0013 Output relays 0 to 1F or
1FF
1- F13
0014 Output information for
threshold : V>
0 to FFFF 1 - F17
0015 Output information for
threshold : V>>
0 to FFFF 1 - F17
0016 Output information for
threshold : V>>>
0 to FFFF 1 - F17
0017 Output information for
threshold : V<
0 to FFFF 1 - F47
0018 Output information for
threshold : V<<
0 to FFFF 1 - F47
0019 Output information for
threshold : V<<<
0 to FFFF 1 - F47
001A Output information for
threshold : V0>
0 to FFFF 1 - F16