Technical Guide P92x/EN CT/E11
Modbus Protocol
MiCOM P921-P922-P923 Page 27/118
1.7.4.3 Zero sequence overvoltage protection (P921- P922 and P923)
Address Group Description
Settings
range
Step Unit Format
Default
settings
0260 Vo> configuration 0-1 1 - F24 0
0261 Threshold Vo> 5 to 1300
or
20 to
4800
1
or
5
V/10 F1 50
or
200
0262 Type of temporisation 0 to 1 1 - F27 0
0263 TMS value for Vo> 5 to 1000 5 1/10 F1 10
0264 tRESET temporisation 0 to 10000 1 1/100 s F1 1
0265 Vo> temporisation 0 to 59999 1 1/100 s F1 4
0266 to
026F
Reserved 0
0270 Vo>> configuration 0-1 1 - F24 0
0271 Threshold Vo>> 5 to 1300
or
20 to 4800
1
or
5
V/10 F1 50
or
200
0272 Vo>> temporisation 0 to 59999 1 1/100 s F1 4
0273 to
027F
Reserved 0
0280 Vo>>> configuration 0-1 1 - F24 0
0281 Threshold Vo>>> 5 to 1300
or
20 to 4800
1
or
5
V/10 F1 50
or
200
0282 Vo>>> temporisation 0 to 59999 1 1/100 s F1 4
0283 to
028F
Reserved 0