P92x/EN CT/E11 Technical Guide
Modbus Protocol
Page 26/118 MiCOM P921-P922-P923
1.7.4.2 Overvoltage protection (P921 -P922 and P923)
Address Group Description
Settings
range
Step Unit Format
Default
settings
0230 V> configuration 0-2 1 - F55 0
0231 Threshold V> 50 to 2000
or
200 to 7200
1
or
5
V/10 F1 1300 or
4800
0232 Type of temporisation 0 to 1 1 - F27 0
0233 TMS value for V> 5 to 1000 5 1/10 F1 10
0234 tRESET temporisation 0 to 10000 1 1/100 s F1 1
0235 V> temporisation 0 to 59999 1 1/100 s F1 4
0236 to
023F
Reserved 0
0240 V>> configuration 0-2 1 - F55 0
0241 Threshold V>> 50 to 2600
or
200 to 9600
1
or
5
V/10 F1 1300 or
4800
0242 V>> temporisation 0 to 59999 1 1/100 s F1 1
0243 to
024F
Reserved 0
0250 V>>> configuration 0-2 1 - F55 0
0251 Threshold V>>> 50 to 2600
or
200 to 9600
1
or
5
V/10 F1 1300 or
4800
0252 V>>> temporisation 0 to 59999 1 1/100 s F1 1
0253 to
025E
Reserved 0
025F V> Hysteresis 95 to 98 1 % or
1/100
F1 98