Technical Guide P92x/EN CT/E11
Modbus Protocol
MiCOM P921-P922-P923 Page 25/118
1.7.4 Page 2 : Protective functions - Remote settings for group 1.
1.7.4.1 Undervoltage protection (P921- P922 and P923)
Address Group Description
Settings
range
Step Unit Format
Default
settings
0200 Setting group
n°1
V< configuration 0-2 1 - F55 0
0201 Threshold V< 50 to
1300 or
200 to 4800
1
or
5
V/10 F1 50
or
200
0202 Type of temporisation 0 to 1 1 - F27 0
0203 TMS value for V< 5 to 1000 5 1/10 F1 10
0204 tRESET temporisation 0 to 10000 1 1/100 s F1 10
0205 V< temporisation 0 to 59999 1 1/100 s F1 4
0206 to
020F
Reserved 0
0210 V<< configuration 0-2 1 - F55 0
0211 Threshold V<< 50 to 1300
or
200 to 4800
1
or
5
V/10 F1 50
or
200
0212 V<< temporisation 0 to 59999 1 1/100 s F1 1
0213 to
021F
Reserved 0
0220 V<<< configuration 0-2 1 - F55 0
0221 Threshold V<<< 50 to 1300
or
200 to 4800
1
or
5
V/10 F1 50
or
200
0222 V<<< temporisation 0 to 59999 1 1/100 s F1 1
0223 to
022E
Reserved 0
022F V< Hysteresis 102 to 105 1 % or
1/100
F1 102