P92x/EN CT/E11 Technical Guide
IEC 60870-5-103
Page 114/118 MiCOM P921-P922-P923
- Trip F1 : INF <113>; TYP <2>; COT<1>,*
- Start F2 : INF <114>; TYP <2>; COT<1>,
- Trip F2 : INF <115>; TYP <2>; COT<1>,*
- Start F3 : INF <116>; TYP <2>; COT<1>,
- Trip F3 : INF <117>; TYP <2>; COT<1>,*
- Start F4 : INF <118>; TYP <2>; COT<1>,
- Trip F4 : INF <119>; TYP <2>; COT<1>,*
- Start F5 : INF <120>; TYP <2>; COT<1>,
- Trip F5 : INF <121>; TYP <2>; COT<1>,*
- Start F6 : INF <122>; TYP <2>; COT<1>,
- Trip F6 : INF <123>; TYP <2>; COT<1>,*
- Frequency non measurable : INF <124>; TYP <2>; COT<1>,
- Trip df/dt 1 : INF <192>; TYP <2>; COT<1>,*
- Trip df/dt 2 : INF <193>; TYP <2>; COT<1>,*
- Trip df/dt 3 : INF <194>; TYP <2>; COT<1>,*
- Trip df/dt 4 : INF <195>; TYP <2>; COT<1>,*
- Trip df/dt 5 : INF <196>; TYP <2>; COT<1>,*
- Trip df/dt 6 : INF <197>; TYP <2>; COT<1>,*
Auto-recloser Indications (monitor direction) :
- CB in O/O (« closed ») position : INF <140>; TYP <1>; COT<1>,
- CB in F/O (« open ») position : INF <141>; TYP <1>; COT<1>,
- Trip TC : INF <142>; TYP <1>; COT<1>,
- Close TC : INF <143>; TYP <1>; COT<1>
5.1.2 System State
List of processed data, following a General interrogation, is given below: it is a
sub-assembly of the spontaneous messages.
Status indications (monitor direction) :
- Local parameter Setting active : INF <22>; TYP <1>; COT<9>
- Setting Group number 1 active : INF <23>; TYP <1>; COT<9>
- Setting Group number 2 active: INF <24>; TYP <1>; COT<9>
- Auxiliary input 1 : INF <27>; TYP <1>; COT<9>
- Auxiliary input 2 : INF <28>; TYP <1>; COT<9>
- Logical input 1 : INF <161>; TYP <1>; COT<9>
- Logical input 2 : INF <162>; TYP <1>; COT<9>
- Logical input 3 : INF <163>; TYP <1>; COT<9>