Technical Guide P92x/EN CT/E11
IEC 60870-5-103
MiCOM P921-P922-P923 Page 115/118
- Logical input 4 : INF <164>; TYP <1>; COT<9>
- Logical input 5 : INF <165>; TYP <1>; COT<9>
- Logical output 1 : INF <176>; TYP <1>; COT<9>
- Logical output 2 : INF <177>; TYP <1>; COT<9>
- Logical output 3: INF <178>; TYP <1>; COT<9>
- Logical output 4: INF <179>; TYP <1>; COT<9>
- Logical output 5: INF <180>; TYP <1>; COT<9>
- Logical output 6: INF <181>; TYP <1>; COT<9>
- Logical output 7: INF <182>; TYP <1>; COT<9>
- Logical output 8: INF <183>; TYP <1>; COT<9>
- Logical output 9: INF <184>; TYP <1>; COT<9>
Fault Indications (monitor direction) :
- General Start / pick-up : INF <84>; TYP <2>; COT<9>
Auto-recloser Indications (monitor direction) :
- CB in O/O (« closed ») position : INF <140>; TYP <1>; COT<1>,
- CB in F/O (« open ») position : INF <141>; TYP <1>; COT<1>,
- Trip TC : INF <142>; TYP <1>; COT<1>,
- Close TC : INF <143>; TYP <1>; COT<1>