EasyManua.ls Logo

Areva MiCOM P921 - Page 339

Areva MiCOM P921
376 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Guide P92x/EN CM/E11
Commissioning Guide
MiCOM P921-P922-P923 Page 17/28
abcd
5.3.2 MiCOM P921-P922-P923 relay parameters
Note the settings of the MiCOM P921-P922-P923 relays in the tables below.
Settings
[59] OVERVOLTAGE
Default values
Group 1 Group 2 (P922-P923)
1
st
stage activated No No / AND / OR * No / AND / OR *
1
st
overvoltage stage 130.0V if H1**
480.0V if H2
VV
Time delay type DMT DMT/IDMT * DMT/IDMT *
TMS 1.0
tRESET V> 0.01s Secs Secs
tV>= 0.04s Secs Secs
2
nd
stage activated No No / AND / OR * No / AND / OR *
2
nd
overvoltage stage 130.0V if H1**
480.0V if H2
VV
tV>>= 0.01s Secs Secs
3
rd
stage activated No No / AND / OR * No / AND / OR *
3
rd
overvoltage stage 130.0V if H1**
480.0V if H2
VV
tV>>>= 0.01s Secs Secs
Hysteresis 0.98
Settings
[27] UNDERVOLTAGE
Default values
Group 1 Group 2 (P922-P923)
1
st
stage activated No No / AND / OR * No / AND / OR *
1
st
undervoltage stage 5.00V if H1**
20.0V if H2
VV
Time delay type DMT DMT/IDMT * DMT/IDMT *
TMS 1.0
tRESET V< 0.01s Secs Secs
tV<= 0.04s Secs Secs
2
nd
stage activated No No / AND / OR * No / AND / OR *
2
nd
undervoltage stage 5.00V if H1**
20.0V if H2
VV
tV<<= 0.01s Secs Secs
3
rd
stage activated No No / AND / OR * No / AND / OR *
3
rd
undervoltage stage 5.00V if H1**
20.0V if H2
VV
tV<<<= 0.01s Secs Secs
Hysteresis 1.02
* Delete as appropriate
** H1 = 57-130V voltage range H1 = 220-480V voltage range

Related product manuals