SPECIFICATIONS FOR ARGUS TECHNOLOGIES’ SWITCH MODE RECTIFIER RSM 48/50 (UPF)
Output
Voltage: 42 - 62 VDC (test)
50 - 60 VDC (equalize)
48 - 57 VDC (float)
Current: 50 Amps DC nominal
Power: 3000 Watts continuous/module
Regulation: +/- 0.02% line and load (static, zero slope)
<1% deviation for 50 to 100% load step (dynamic)
Response Time: 2 msec to 0.1% of output for 50 to 100% load step
Time Stability: 0.2% per year
Temp. Stability: 100 ppm/degree C over the operating range
Noise: Less than 23 dBrnC (Voice Band)
10mVRMS 10kHz to 10MHz (Wide Band)
150mVp-p 10kHz to 100MHz
EMI: The unit meets requirements of FCC Rules
Part 15, Subpart B, Class A
Breaker Rating: 60 Amp, 5000 Amp interrupting capacity at 65 VDC
In Accordance with FCC requirements, we provide the following statement as specified in the FCC guide-
lines for conformance to Part 15, Class A:
NOTE: This equipment has been tested and found to comply with the
limits for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio
frequency energy and if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is
likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.
Any changes or modifications to this equipment not expressly approved in this manual could void FCC
compliance.
ARGUS TECHNOLOGIES 010-511-B1 Rev A Page 1 of 3