Input
Voltage: 184 to 264 VAC (47 to 63 Hz)
Current: 13A (240 VAC Nominal) @ 2800 Watts output power
14A (240 VAC Nominal) @ 3000 Watts output power
15A (208 VAC Nominal) @ 2800 Watts output power
16A (208 VAC Nominal) @ 3000 Watts output power
Power Factor: >0.99 for 40%-100% load
>0.96 for 20%-40% load
T.I.F. (Current): <100 at 100% load
Efficiency: 90% minimum 50 to 100% load
Hold-over time: 30ms from loss of AC line
Source Impedance: 5% inductive or resistive
Soft Start: Approximately 10% per second
Start Delay: 0-250 sec. (10 second increments)
Input Transient Suppression: Tested to IEEE/ANSI C62.41 Category B
Breaker Rating: 25 Amp, 10,000 Amp interrupting capacity at 250 VAC
Recommended Feeder Breaker: 25 Amps or greater (240 VAC)
Miscellaneous
Size: 3 Module Shelf: 267mm H x 432mm W x 381mm D
(10.5" H x 17.0" W x 15" D)
4 Module Shelf: 267mm H x 546mm W x 381mm D
(10.5" H x 21.5" W x 15" D)
Module: 262mm H x 132mm W x 343mm D
(10.3" H x 5.2" W x 13.5" D)
Mounting: Separate shelves are required
for 19" or 23" mounting.
Weight: 4 Module Shelf: 16 kg (36 lb.)
3 Module Shelf: 14 kg (31 lb.)
Module: 12 kg (26 lb.)
Acoustic Noise: 60 dBa at 1m (3 ft)
Alarm/Control Connections: 60 VDC, 0.5 A maximum
ARGUS TECHNOLOGIES 010-511-B1 Rev A Page 2 of 3