EasyManua.ls Logo

Argus RSM 48 UPF - Page 5

Argus RSM 48 UPF
58 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Input
Voltage: 184 to 264 VAC (47 to 63 Hz)
Current: 13A (240 VAC Nominal) @ 2800 Watts output power
14A (240 VAC Nominal) @ 3000 Watts output power
15A (208 VAC Nominal) @ 2800 Watts output power
16A (208 VAC Nominal) @ 3000 Watts output power
Power Factor: >0.99 for 40%-100% load
>0.96 for 20%-40% load
T.I.F. (Current): <100 at 100% load
Efficiency: 90% minimum 50 to 100% load
Hold-over time: 30ms from loss of AC line
Source Impedance: 5% inductive or resistive
Soft Start: Approximately 10% per second
Start Delay: 0-250 sec. (10 second increments)
Input Transient Suppression: Tested to IEEE/ANSI C62.41 Category B
Breaker Rating: 25 Amp, 10,000 Amp interrupting capacity at 250 VAC
Recommended Feeder Breaker: 25 Amps or greater (240 VAC)
Miscellaneous
Size: 3 Module Shelf: 267mm H x 432mm W x 381mm D
(10.5" H x 17.0" W x 15" D)
4 Module Shelf: 267mm H x 546mm W x 381mm D
(10.5" H x 21.5" W x 15" D)
Module: 262mm H x 132mm W x 343mm D
(10.3" H x 5.2" W x 13.5" D)
Mounting: Separate shelves are required
for 19" or 23" mounting.
Weight: 4 Module Shelf: 16 kg (36 lb.)
3 Module Shelf: 14 kg (31 lb.)
Module: 12 kg (26 lb.)
Acoustic Noise: 60 dBa at 1m (3 ft)
Alarm/Control Connections: 60 VDC, 0.5 A maximum
ARGUS TECHNOLOGIES 010-511-B1 Rev A Page 2 of 3