14.3. Calibrating of the new oil vessel load cell
Tare function
(a) Place empty recovered oil vessel
(b) Switch ON Ariazone unit while holding "UP" button until the unit
display’s 'TAr 2'.
(c) Release 'UP' key.
(d) Press 'START' button after sound signal and display will indicate 'DONE'
Span function
(a) Place 200ml of oil into the recovered oil vessel
(b) Switch ON Ariazone unit while holding "DOWN" button until the unit
display’s 'SPn 2'.
(c) Set the correct weight 200ml by pressing the 'UP' or "DOWN" buttons. The display (2) should
indicate same weight of 0.200.
(d) Press 'START' button to lock in correct weight
14.4. Adjust Date/Time (only where printer fitted)
Switch ON the unit (19) while holding both "UP"&"DOWN" switches depressed to enter into
date/time adjusting mode. By using "UP" and "DOWN" keys simply adjust: Year, Month, Date,
Hours, Minutes and press "START" to confirm.
Thank you for reading the Ariazone 5001 operator manual.
If you are not sure or do not fully understand any part of this manual,
please contact Ariazone International or appointed distributor.
Ariazone Head office Australia Ariazone Manufacturing Europe
Ariazone International Ariazone International Europe
3/55 Northgate Drive Thomastown 15 ti Curpus,6000 Ohrid Macedonia
Melbourne Australia 3074
Telephone: ++ 389 46 230 320
Facsimile: ++ 389 46 230 321
Telephone: + + 61-3-9464 5688 E-mail: ariazone_info@mt.net.mk
Facsimile: + + 61-3-9464 5788 Web: www.ariazone.com.mk
E-mail: sales@ariazone.com
Web: www.ariazone.com

Other manuals for ariazone 5001

Related product manuals