ARICO Technology Co., Ltd. -9-
1-4-9 PID auto tuning function
To get the optimal PID value in some system, it is possible to execute "PID
auto tuning" function at first use or heater system change
After finishing auto tuning, the optimal PID will be saved into the instrument
and memory and will use the latest PID value for optimal temperature control.
PID auto tuning function:
(1)PV must be lower than 120°C or 180°F。
(2)SV must be higher than PV for 80°C or 100°F
(3)Set parameter TUN into YES
PS: During PID auto tuning execution, the decimal point of PV will flash. After
the instrument gets the optimal PID, the decimal point turns off and the
instrument returns to auto temperature control.