-6-
1-4-2 Soft start (Heater dehumidify) function
To avoid the humidity burning the heater out, the soft start function could
output a lower current to dehumidify the heater when the power turned on.
Soft start condition:
The soft start percentage (SSP) and time (SST). After power turned on, if
SV > PV ; PV < 120°C, manual and PID tuning function are disabled, the soft
start will be executed. Set SST to zero to stop soft start function.
Soft start action state:
Before SST time countdown completes, soft start outputs in 1%/sec
accumulative mode until it gets SSP setting value. The accumulative mode
will stop and wait SST time to complete countdown.
Soft start stop on halfway:
Press F for 2 sec to close soft start.
1-4-3 Control mode
Auto mode: The instrument performs PID auto temperature control
Manual mode: Manually adjust output percentage (UNIT displays “P”) via NOP
to hold the temperature.
Manual/Auto mode switch: Press display interchange for 2 sec.
1-4-4 Communication
Communication mode: Modbus ASCII / RTU
Baud rate: 9600/19200/(value of production38400)
ID: 1-250(value of production: 1)
According to the procedure of HMI