7ExTensor
Only suitable cable and line entries and blind plugs certied according to the ATEX/IECEx protection class may be used for the
introduction of cables (lines) - the diameters must correspond to the cables used.
Unused housing entries (threaded holes) which are intended for the use of cable and line entries must be sealed with suitable blind
plugs certied according to the ATEX/IECEx protection class. When selecting the correct cable and line entry, EN IEC 60079-14 must
also be observed. The cable and line entries as well as blind plugs must be suitable for an operating temperature of at least +80°C.
DANGER! On the back of the drive, there is a blind plug to close the handwheel option for
equipment variants without a handwheel. This may not be removed or altered. See also
Chapter 6 - Handwheel section.
Another transport protection sticker is located on top of the drive hood to protect the sight
glass during transport / storage. This must also be removed prior to commissioning. Opera-
tion with the sticker or parts thereof is not permitted. Non-compliance can lead to serious
accidents and damage to property - The ATEX/IECEx approval of the device becomes void
in the event of non-compliance or misuse.
Suitable products (cable entries, blind plugs) are available as accessories from ARIS, tailored to the ATEX/IECEx products. If requi-
red, these are loosely enclosed with the drive. The delivery is always unassembled.
Please note the correct assembly. The cable entries used must always be designed for the connecting cables and correspond to the
cable diameters.
3.3 Performance data
ARIS actuators type ExTensor correspond in their basic form (primary version) up to 40Nm
torque - without gear extensions, the EU type examination certicate number IBExU22A-
TEX1066 X. - see appendix of these operating instructions. Variants with torques of
50 ... 500Nm (secondary versions) correspond to the primary version, but are supplemen-
ted by an externally mounted gear extension (planetary gear stage).
Voltage supply AC 85…265 V AC (50/60 Hz) End position cutoff Digital
Voltage supply DC 24 V DC (±10%) Position feedback Digital, contactless
Max. power consumption 60 VA Connection Cable/wire entry: 3x M25x1.5
Torque 5 Nm…500 Nm Ambient temperature -20° C…+60° C
Actuating time 1s/90°…150s/90° IP protection class IP65/IP67
Motor type BLDC