EasyManua.ls Logo

ARIS ExTensor - Declaration of Incorporation

ARIS ExTensor
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
37ExTensor
9. Declaration of incorporation
Telefon +49(0)2241‐25186‐0
Telefax +49(0)2241‐25186‐99
Rotter Viehtrift 9
D‐53842
Troisdorf
ARIS Stellantriebe GmbH
www.stellantriebe.de
ECDeclaration of Conformity
Electric actuator
Designation:
Herewith we declare
ExTensor and identical
Series:
ARIS Stellantriebe GmbH Name:
Rotter Viehtrift 9, D ‐ 53842 Troisdorf Adress:
Troisdorf 19.09.2023
______________________________________
i.V. R. Schulte (Quality and product safety)
2G in type of protection flameproof enclosure "db" for use in zone 1
2D in type of protection dust explosion protection by enclosure "tb" for use in zone 21
to which this declaration refers, complies with the essential requirements of the following European
directives by being in accordance with the specified harmonized standards:
Dir 2014/34/EU (ATEX)
EN IEC 60079‐0:2018 (IEC 60079‐0:2017, Ed. 7.0)
EN 60079‐1:2014 (IEC 60079‐1:2014, Ed. 7.0)
EN 60079‐31:2014 (IEC 60079‐31:2013, Ed. 2.0)
EN ISO/IEC 80079‐34:2020
The actuators mentioned are group II and III devices in the sense of EN IEC 60079‐0 and comply with the
therein specified device protection levels
Gb, Group II, Subgroup IIC as well as Db, Group III, Subgroup IIIC
In accordance with Directive 2014/34/EU, they meet the explosion protection requirements for Group II
equipment and the following categories
in sole responsibility that the product
The explosion protection marking for the actuators of this series is as follows
II 2G Ex db IIC T6 Gb
II 2D Ex tb IIIC T80 °C Db
Ta ‐20 °C ... +60 °C
The conformity assessment with regard to Dir
2014/34/EU has been confirmed by the type examination
report
IBExU22ATEX1066X / 0.
Dir 2011/65/EU
EN IEC 63000:2018
Dir 2014/30/EU
EN 61000‐6‐5:2015/AC:2018‐01
The technical documentation has been fully created
.
This declaration becomes invalid if the actuator is modified in any way that has not been approved by us
or if the actuator is not used for the intended purpose.