19
Technical Installation Instructions and User Guide
GB
TECHNICAL DESCRIPTION
Technical Data as per standard 12897: 2006
TANK 1S/2S 200 L 300 L 450 L
Top coil
Coil capacity
Ltr 6 6 7,5
Coil surface
m
2
0,8 0,8 1
Exchanger output (En 15332)
kW 14,2 14,2 19,7
Exchanger output (En 12897)
kW 13,8 13,8 17,4
Coil resistance
mbar 9 9 10
Bottom coil
Coil capacity
Ltr 6,9 9,6 11,8
Coil surface
m
2
0,9 1,3 1,6
Exchanger output (En 15332)
kW 20,7 25,4 34,1
Exchanger output (En 12897)
kW 16,9 19,4 21,3
Coil resistance
mbar 12 15 17
Max. working pressure
bar 10 10 10
Thermal loss kWh/24
1,49 2,13 2,64
Maximum temperature
°C 90 90 90
Weight Kg (1S/2S) 69/75 94/100 116/127